The Room Controller QuicKits use OAC (C1, C2, C3) or OAWC (W1, W2, W3) model sensors to allow for occupancy control.
Specifications
Voltage
Electrical
Connections
Operating Environment
N
ote:
The Room Controller connects to standard GG occupancy sensors, through the OCC-RJ45 Input/Output Device.
Ceiling Sensor Mounting
OAC sensors can be mounted to the ceiling, junction box or round fixture with raceway. Optimum mounting height is 8-10
feet. Do not mount over 12 feet.
Mount at fixture height to avoid obstucting view.
Mount the sensor at least 4-6 feet from air supply ducts to avoid false activation.
9850-000362-06 page 7
October 2022
10-30 VDC (24 VDC supplied from
Room Controller)
Class 2, LPS
Wire leads connect to a provided
OCC-RJ45 Input/Output Device.
The Input/Output Device contains
two QuickConnect ports.
32° F to 104° F (0° to 40° C)
For indoor use only.
Room Controller
www.cooperlighting.com