Bringing the Room Controller Online
The Room Controller is pre-programmed and ready for operation out-of-the-box. If no adjustments are done, the unit will
operate from occupancy sensors, daylighting and wallstations.
To obtain maximum energy efficiency and occupant satisfaction, we recommend that you complete this short checklist to
verify the unit is operating optimally for the space being controlled.
1.
Initial Power Up Response
Apply power to the Room Controller.
Verify that all lighting loads turn on to full for 3 seconds before beginning normal operation.
2.
Verify Occupancy Sensor Operation
Verify that the occupancy sensor has been located properly to prevent false activation.
Wait 2 minutes from power-up, then place OAC or OAWC sensors in Test Mode
by moving DIP Switch 10 out of its current position, wait 3 seconds, then put
back into its original position.
Move around the controlled area, verifying that the ocupancy sensor LEDs flash with each motion and stop flashing when you
stand still.
If not already ON, turn lighting ON from the wallstation controls. For any stations with Quiet Time buttons, make sure that Quiet
Time Mode is de-activated (LED is not lit).
Leave the room and wait approximately one minute for the lighting to turn OFF.
If lighting does not turn OFF, refer to "Room Controller Troubleshooting" on page 24. Sensors will automatically exit Test Mode after a
period of 5 to 10 minutes (timing is dependent on sensor model) and begin automatically adjusting based on occupancy patterns.
3.
Verify Wallstation Operation
Check each wallstation for proper operation of intended loads.
4.
Set Minimum and Maximum Trim levels
Trim levels have been preset to approximately 90% maximum. Additional energy savings can be gained by adjusting the trim further if
electric
lighting contribution is over the target illuminance for the space.
Locate the position of the trim level adjustment dials on the Room Controller.
Trim levels are being adjusted at night or shades have been used to darken the space during daylight hours.
Using the wallstations, turn ON all controlled lighting. For fluorescent lighting loads, wait one minute to allow lamps to warm up.
Using a small screwdriver, twist the maximum trim dial counter clockwise, then fully clockwise again. The lights will go full bright
and the Room Controller will enter Adjustment Mode.
Turn the maximum trim adjustment dial counter-clockwise in small increments until the light level is at the desired maximum level.
Turn the minimum trim dial clockwise then fully counter clockwise. The light level in the room will go full dim.
Turn the minimum trim dial clockwise in small increments until you begin to notice the light level increasing in the monitored
space, then turn the dial slightly counter clockwise from where this change begins.
Save the new trim settings and go back to normal operation by pressing the "All OFF" button on any wallstation.
If "All OFF" is not pressed, the controller will automatically save these settings after two minutes.
9850-000362-06 page 19
October 2022
Room Controller Verification Checklist
Room Location: ____________________
ON
1
2
3
4
5
6
7
8
9 10
1 2 3 4 5 6 7 8 9 10 11 12
Switchpack
White
Red
Receptacle
BMS/Out
Black
Sensors
Green
Sensors
Slider
Station
Wallstations
-
A/V
+
Mode
-
Demand
Response
+
-
Alert
Mode
+
-
Time
+
Clock
Energy Options DIP Switch
Demand Response
Occupancy
Not Used
1 2
3
4
Default 10%
Occ
20%
Vac (default)
30%
40%
0-10V Dimming Outputs
-
-
-
+
+
+
Dimmer 3
Dimmer 2
Dimmer 1
-
-
-
Dimmer 3
+
Dimmer 2
+
Dimmer 1
+
0-10V Dimming
www.cooperlighting.com
Room Controller