Room Controller
2.
After lighting is OFF , press the "All OFF" button four times as if you were saying the separated syllables of the word
"Emergency" {E-MER-GEN-CY}.
3.
The emergency relay will turn ON in response to this command verifying that the emergency load control relay is
operational.
4.
Once the test is complete, turn OFF the emergency load by pressing the "All OFF" button again.
5.
If left in Test Mode, the Room Controller will automatically exit the emergency test after 1 minute and turn OFF the
emergency load.
System LED Indicators and Reset Buttons
The Room Controller has an onboard status indicator and reset button to assist with troubleshooting. In addition, other
components within the Room Controller package have LED indicators that may indicate specific functions.
Room Controller Troubleshooting
Issue
Lights will not turn ON
automatically
Lights will not
turn ON from
wallstations
Lighting turns
ON but is not
the right zone
Emergency lighting
does not turn ON
with the correct zone
(RC3DE only)
If still having trouble with lighting turning ON, call Technical Services at 1-800-553-3879
Lights will not
remain ON (Lights
turn OFF approx. 30
seconds after the On
command)
Lights will not
remain ON (Lights
turn OFF approx. 60
minutes after the ON
command)
If still having trouble with lighting remaining ON, call Technical Services at 1-800-553-3879
www.cooperlighting.com
Possible Causes
The default mode for occupancy control is Vacancy Mode. Use Energy Option DIP Switch 3
Vacancy Mode set
to place in Occupancy Mode. In Occupancy Mode, Load 1 (yellow) will trigger automatically
on Room Controller
upon occupancy.
Vacancy Mode
If a sensor is being used that has an Automatic/Manual Mode, ensure that the sensor is in
set on Occupancy
Automatic Mode.
Sensor
Verify that all Click & Go Connections are connected to the correct ports for the accessories
Connection Issue
being used.
Verify that all Click & Go Connections are connected to the correct ports for the accessories
Connection Issue
being used.
Verify that the Room Controller status LED is flashing. If it is flashing, press and release the
Microprocessor
reset button and verify that lighting turns ON for 3 seconds. If there is no response, contact
technical support.
Power Interruption
If the Room Controller status LED is not flashing, check incoming voltage and/or wiring.
Verify that Load 1, Load 2, and Load 3 have been wired to the appropriate loads in the space
Wiring
to meet your application.
The Room Controller controls the emergency lighting along with the normal lighting Load 1
(yellow). Ensure that Load 1 (yellow) is connected to the load that the emergency lighting
Wiring
needs to operate with.
Verify that the occupancy sensor LEDs are flashing when motion is occurring.
The controller
senses that there
Make sure that the occupancy sensor coupler is connected to the correct wires from the
is an occupancy
occupancy sensor.
sensor
connected but is
If the occupancy sensor being used has an Auto/Manual selection, verify that the occupancy
not
sensor is in Auto Mode.
seeing an occupied
signal from the
Verify that you are not using a VAC model sensor.
sensor.
When the Room Controller does not have an occupancy sensor connected, it relies on button
presses or time clock input for lighting control. If the time clock is open and there is no
Time Clock Open
occupancy sensor. Button presses automatically have a 1 hour timer.
Suggestions
Greengate
9850-000362-06 page 24