Room Controller
7 .
Repeat this process for each of the dimming zones as necessary.
8.
To save the new levels and exit Commissioning Mode, press the "All OFF" button on any wallstation. If "All OFF" is not
pressed, the controller will save the settings and exit Commissioning Mode after two minutes.
9.
The room controller will now operate with the new daylight levels.
White
Switchpack
Receptacle
Red
BMS/Out
Black
Sensors
Green
Sensors
Slider
Station
Wallstations
-
A/V
+
Mode
-
Demand
+
Response
-
Alert
+
Mode
-
Time
+
Clock
Energy Options DIP Switch
Demand Response
Occupancy
Not Used
1
2
3
4
Default 10%
Occ
20%
Vac (default)
30%
40%
0-10V Dimming Outputs
-
-
-
+
+
+
Dimmer 3
Dimmer 2
Dimmer 1
It is possible to disable daylight dimming for any dimming zone allowing the dimmer to respond only to the raise/lower
N
ote:
controls and wallstation presets. To disable daylight dimming, on the Room Controller, twist the desired dimmer's gain
adjustment dial fully clockwise, and then fully counter clockwise. When setting daylight levels with the HHPRG-RC
remote, avoid pressing the Zone Level adjustment buttons for the disabled zone. If adjusted in error, simply reset the
gain adjustment dial again.
www.cooperlighting.com
Daylight Gain
Adjustment
6
5
4
3
2
1
Dimmer 3
-
Dimmer 2
-
Dimmer 1
+
+
0-10V Dimming
Dimmer 3
-
Dimmer 2
-
Dimmer 1
-
+
+
+
0-10V Dimming
-
+
Greengate
9850-000362-06 page 22
October 2022