Descargar Imprimir esta página

Cooper Lighting Solutions Greengate RC3 Instrucciones De Instalación página 4

Publicidad

Idiomas disponibles

Idiomas disponibles

Room Controller
Mounting
Mount the Room Controller above the entrance door of the
room being controlled.
Connect any necessary line and low voltage conduit directly
to the Room Controller.
Load Wiring
Before Connecting Circuits:
1.
Connect lighting load wiring directly to the circuit breaker to ensure there are no shorts or miswires.
2.
For any 0-10V dimmable loads, separate the purple and pink* leads for each zone controlled. All lighting loads should be
at full bright output.
3.
Isolate one dimming zone and temporarily connect the purple and pink* 0-10V leads together.
4.
Verify that the controlled zone dims to its lowest output level, then label the zone wiring for easy identification.
Disconnect the 0-10V leads for the zone under test and then repeat for remaining dimming zones.
www.cooperlighting.com
Line Voltage
Emergency
Line Voltage
(RC3DE only)
CAUTION
Greengate
Low Voltage
(Class 2)
6
White
Switchpack
Red
Receptacle
BMS/Out
5
Black
Sensors
Sensors
Green
Slider
Station
4
Wallstations
-
A/V
Mode
+
-
3
Demand
Response
+
-
Alert
Mode
+
-
Time
Clock
+
2
1
Energy Options DIP Switch
Demand Response
Occupancy
Not Used
1
2
3
4
Default 10%
Occ
20%
Vac (default)
30%
40%
0-10V Dimming Outputs
+
-
+
-
+
-
Dimmer 3
Dimmer 2
Dimmer 1
Dimmer 3
-
Dimmer 2
-
Dimmer 1
-
+
+
+
0-10V Dimming
9850-000362-06 page 4
October 2022

Publicidad

loading