Greengate
Normal Power Connections
The feeding circuit will provide power to the controlled loads
as well as to the Room Controller's microprocessor. The
maximum combined load of the three relays onboard the
Room Controller should not exceed 20A.
Connect line voltage wiring to the provided leads, matching
your room configuration to load 1, 2 and 3 according to
your lighting layout and/or diagram on the Room Controller
QuicKit.
Connecting Emergency Power Line Voltage
The RC3DE model supports a 3A emergency relay. This is a
UL 924 listed solution for emergency lighting control.
Under normal power operation, the emergency load will
track operation to the load tied to the yellow lead (load 1).
When normal power fails, the emergency relay will close
and the load will be forced on to full brightness.
Connecting 0-10V Load Wiring
The RC3D and RC3DE models allow for connection of up
to three 0-10V dimming zones depending on the model.
Dimming outputs are independent of relay control to
allow maximum flexibility in application. Switched zones
and dimmed zones do not need to overlap in the Room
Controller architecture as relays and dimmers are controlled
separately.
Route the 0-10V purple and pink* wires through one of
the provided conduit knockouts in the low voltage section.
0-10V terminal blocks are removable for ease of wiring.
Connect the 0-10V purple wire to the positive location and
the pink* wire to the negative location on the first dimmer
terminal block. Repeat for additional dimming zones.
Load 3
Load 2
Load 2
Dimmer 1
Dimmer 2
Load 1
Load 1
Dimmer 1
Dimmer 2
Load 1
Load 1
Dimmer 1
Dimmer 2
Load 1
Load 1
Dimmer 1
Dimmer 2
9850-000362-06 page 5
October 2022
Load 2
Dimmer 3
Load 1
Dimmer 3
Load 1
Dimmer 3
Load 1
Dimmer 3
White
Switchpack
Receptacle
Red
BMS/Out
Black
Sensors
Sensors
Green
Slider
Station
Wallstations
-
A/V
+
Mode
-
Demand
+
Response
-
Alert
+
Mode
-
Time
+
Clock
Energy Options DIP Switch
Demand Response
Occupancy
Not Used
1
2
3
Default 10%
Occ
20%
Vac (default)
30%
40%
0-10V Dimming Outputs
-
-
+
+
+
Dimmer 3
Dimmer 2
Dimmer 1
(RC3DE Model Shown)
N
ote:
For daylight dimming applications,
dimmer 1 should be the zone closest
to the window. Dimmer 3 is the zone
furthest from the window.
Zone Wallstations & Scene Wallstations
Half Lights
Full Lights
Undercabinet
Specifications
Voltage
Electrical
Connections
Installation
Operating Environment
Room Controller
6
5
4
3
2
1
4
-
Dimmer 3
-
Dimmer 2
-
Dimmer 1
-
+
+
+
0-10V Dimming
Dimmer 3 Dimmer 2 Dimmer 1
-
-
-
+
+
+
0-10V Dimming
0-10V Pink* (-)
0-10V Violet (+)
Raise
Lower
All OFF
24 VDC supplied from Room
Controller
Class 2, LPS
Two onboard QuickConnect ports
Standard decorator opening
32° F to 104° F (0° to 40° C)
For indoor use only.
www.cooperlighting.com