Sime MIA HE C10 Manual De Uso, Instalación Y Mantenimiento página 95

Ocultar thumbs Ver también para MIA HE C10:

Publicidad

Idiomas disponibles

Idiomas disponibles

EN
6.12
Smoke outlet and combustion air inlet
boilers must be equipped with appropriate smoke flue ducts and combustion air inlet ducts. These ducts are considered
MIA HE C10
an integral part of the boiler and are provided by Sime as an accessory kit, to be ordered separately from the appliance on the basis of
the type permitted and the system requirements.
Permitted types of exhausts and ducts
C53
C53x
B23P
B53P
Outlet
B23P-B53P Combustion air inlet into the atmosphere and smoke outlet to open air
Concentric wall smoke outlet The pipes can start from the boiler but the
C13-C13X
outlets must be concentric or close together (no more than 50 cm) to be
subject to similar wind conditions
Concentric roof smoke outlet The pipes can start from the boiler but the
C33-C33X
outlets must be concentric or close together (no more than 50 cm) to be
subject to similar wind conditions
Outlet and inlet in shared or separate flue pipes but subjected to similar
C43-C43X
wind conditions
Separate wall or roof inlet and outlet in different pressure areas
C53-C53X
the inlet and outlet must never be positioned on opposing walls
NOTE:
C83-C83X
Outlet in single or shared flue or with inlet on wall
C93-C93X
Separate outlet and inlet in shared flue pipe
Type C appliance connected, via conduits, to a collective pipe designed for
more than one appliance. The collective pipe is made up of two conduits
connected to a terminal which also feeds in air from outside the burner and
C(10)3
evacuates the combustion products externally through concentric orifices or
those close enough to result in the same wind conditions
the boiler can be type C(10)3 only with accessory code 6396549
NOTE:
C63-C63X
Outlet and inlet made from pipes which are sold and certified separately
smoke outlet system designed to operate with positive pressure.
P:
appliances and related smoke exhausts installed.
X:
All the measurements are in mm.
m
WARNINGS
– The smoke flue and the connection to the flue pipe must be in compliance with the national and local standards and legis-
lation in force in the country where the appliance will be used.
– The use of rigid ducts which are resistant to temperature, condensate, mechanical stress and are air-tight is compulsory.
– Outlet ducts which are not isolated are a risk of danger.
C43
C43X
C93
C93X
C83
C83X
Description
C43
C43X
C33X
C33
C33X
C13X
C(10)3
C13X
Coaxial duct
Ø 60/100
Ø 80/125
X
X
X
C33
max 0,5 m
C13
C13
Fig. 22
Separate ducts
Ø 80
Ø 60
Ø 50
X
X
X
X
X
X
X
X
95