Example: calculation of the load loss of a MIA HE 40 C10 boiler.
Accessories Ø
Code
Quantity
80 mm
Extension
W. 1000 mm
8077351
7
(horizontal)
Extension
W. 1000 mm
8077351
7
(horizontal)
90° curve
8077450
2
90° curve
8077450
2
Wall terminal
8089501
2
TOTAL
(installation permitted since the total of the load loss of the ac-
cessories used is less than 15 mmH
420
Ø 80
Load loss (mm H
O)
2
Inlet
Outlet
Total
7 x 0,25
-
1,75
-
7 x 0,25
1,75
2 x 0,30
-
0,60
-
2 x 0,40
0,80
0,15
0,50
0,65
5,55
O).
2
210
80
Fig. 24
6.13
Electrical connections
The power cable must be connected to a 230V (±10%) ~ 50 Hz
network, observing L-N polarity and the earth connection. The
network must have an omnipolar switch with category III over-
voltage, in compliance with the installation rules.
If this cable needs to be replaced, an original spare must be re-
quested from Sime .
Therefore only the connections of the original components as
shown in the table are needed. These are to be ordered sepa-
rately from the boiler.
DESCRIPTION
External sensor kit (ß=3435, NTC 10KOhm at
25°C)
Power cable (dedicated)
Remote control EASY HOME (not supplied)
Remote control HOME (not supplied)
Remote control HOME PLUS (not supplied)
m
CAUTION
The maintenance interventions described must ONLY
be carried out the professionally qualified personnel.
a
WARNING
Before carrying out any interventions described:
– set the main system switch to "OFF"
– close the gas valve
– make sure that no hot parts inside the appliance are
touched.
OFF
To facilitate introduction of the connection wires of the optional
components into the boiler:
– remove the screws (1), pull the front panel (2) forwards and
release it from the top by lifting it
2
CODE
8094101
6329477
8092279
8092280
8092281
Fig. 25
1
Fig. 26
97