Descargar Imprimir esta página

EMERYMARK EMP 200 Manual De Operación página 75

Ocultar thumbs Ver también para EMP 200:

Publicidad

Idiomas disponibles

Idiomas disponibles

3.4 Trouble-shooting chart
TROUBLE
Freezing or blockage in
the pipe with propylene
glycol
Compressor starts but
remainsin start windings.
(Single phase only)
Starter burned out.
Starting capacitors burn
out. (Single phase only)
Running capacitors burn
out. (Single phase only)
Unit operates long or con-
tinuously.
Water flowing through
water waste line when unit
is not in operation.
Noisy compressor.
PROBABLE CAUSE
1. Percentage of water above
normal.
1. Low line voltage
2. Improperly wired
3. Runing capacitor shorted
4. Starting capacitor weak
5. High discharge pressure
1. Low line voltage.
2. Excessive line voltage.
1. Voltage too low.
2. Impoper capacitor.
1. Excessive line voltage.
1. Shortage of gas.
2. Dirty condenser.
3. Moisture in system.
4. Compressor failing.
1. Water regulating valve defective.
1. Tubing rattle.
Maintenance
REMEDY
1. Remove and replace all of the solution
according to the percentages
*according to your supplier.
1. Ask power company to increase volta-
ge to no less than 10% below nameplate
rating or install transformer.
2. Check wiring against drawing. Check
wire size.
3. Check by disconnecting runing capa-
citor.
4. Check capacitor, replace.
5. Check water regulating valve; check
water or air condenser and clean, if ne-
cessary. Check discharge shut-off valve
1. Ask power company to increase volta-
ge to not less than 10% below nameplate
rating or install transformer.
2. Ask power company to reduce volta-
ge to maximum of 10% over nameplate
rating.
1. Ask power company to increase volta-
ge to not less than 10% below nameplate
rating or install transformer.
2. Replace capacitor with properly rated
capacitor, as listed in manual.
1. Ask power company to reduce line vol-
tage to not more than 10% above rating
of motor.
1. Repair leak and recharge.
2. Clean condenser.
3. Evacuate and recharge system.
4. Check compressor for proper pressu-
res. If inadequate, replace compressor.
1. Replace water regulating valve.
1. Bend tubes away from contact.
75

Publicidad

loading

Productos relacionados para EMERYMARK EMP 200

Este manual también es adecuado para:

Emp 500Emp 1500Emp 3000