UK
Lift the machine with a pallet truck (or other suitable lifting means), using the specific lifting hooks.
3.
Position the machine on the wall of the cold-room, inserting the evaporating part from the outside into the arranged hole.
4.
5.
Fasten the machine to the wall of the cold-room with appropriate screws (which are supplied).
6.
Seal the perimeter of the wall-mount opening with silicon (having characteristics suitable to the use of the cold-room), in
order to avoid air and/or humidity passage between the conditioned environment and the outside. Figure 6 displays the
outcome of the installation.
4.3.3 Connection to the Electrical Power Supply Network
The electrical power supply (also in terms of voltage and frequency) supplied by the Buyer must be sufficient to correctly supply the
machine. More specifically, it is necessary to implement the following indications:
The supply cable must be extended properly (avoid winding ups and overlaps), in a position that does not risk to incur
collisions or tampering , must not be in proximity of liquids, water, or heat sources, and must not be damaged (if it does get
damaged, have it replaced by qualified personnel).
Arrange for a differential magneto-thermal switch between the supply line and the machine properly sized to the application
and in conformity with the regulation in force of the nation where the machine is installed and make sure that the line voltage
corresponds to the voltage indicated on the plate (see label applied on the machine); allowed tolerance: ± 10% of the
nominal voltage.
WARNING:
It is necessary that the section of the supply cable be adequate to the power absorbed by the machine.
WARNING:
Figure 5 – WTH version, large wall-mount opening
Figure 6 – WTH version, outcome of the installation.
The differential magneto-thermal switch must be placed in the immediate vicinity of the machine, so
that it is clearly visible and accessible to the technician in case of maintenance.
It is mandatory, by law, to connect the machine to an efficient grounding system. We reject any
responsibility due to the failure to comply to the above provision; we reject any responsibility in case
that the electrical system to which the machine is connected, is not built in accordance to the norms in
force.