3.8 I
NSIDE INSTALLATION
Correct indoor installation of the system must observe
the following installation requirements:
-
The site must be adequately dimensioned in order
to allow correct operation of the group as well as
easy access for routine maintenance operations
and eventual repairs. The figure shows the minimum
recommended dimensions for clearance around the
system and the height of the site.
-
Access to the site must allow the introduction of the
complete system using standard transport and
handling devices available in the premises.
-
There must be apertures of adequate dimensions to
ensure continual and efficient recirculation of air.
-
Installation of exhaust piping to the exterior of
limited length and the fewest possible number of
curves is compulsory.
-
The system may be arranged with sufficient passage
space on at least three sides, provided that easy
access and observance of safety regulations are
maintained.
-
The control panel (for automatic sets) must be
positioned so that the instruments are clearly visible
to the operator working near the system (for example,
see ref. 2 and 4 in the figure below).
MPL 111 S
Inside installation
Key:
1 - Casing in painted sheet metal
2 - On board control panel
3 - Foundation
4 - Distribution panel not supplied as
standard (automatic start remote control
switches-Optional)
5 - Cable duct
6 - Air intake
7 - Gas exhaust pipe
8 - Conveyer air expulsion (Solution n°1)
9 - Fan (Solution n°2, see air flow in tab.
"Technical characteristics" par.2.4)
GB
GB
- 21