For the electrical connections, refer to the control unit manual.
The factory configurations can be seen in Table 20.
Factory configurations of the outputs
Uscita
OUT 1
OUT 2
Table 20: Factory configurations of the outputs
7.6.17 - O1: Setting output 1 function
Output 1 communicates an active alarm (it indicates that a system block has
occurred). The output allows the use of a normally open clean contact.
The values and functions indicated in Table 21 are associated with the param-
eter O1.
7.6.18 - O2: Setting output 2 function
Output 2 communicates the motor running status. The output allows the
use of a normally open clean contact.
The values and functions indicated in Table 21 are associated with the
parameter O2.
Configuration of the functions associated with the outputs
OUT1
Output confi-
Activation
guration
condition
No associated
0
function
No associated
1
function
100
Value
2 (fault NO closes)
2 (Pump running NO closes)
OUT2
Output contact
Activation
Output contact
condition
status
Contact always
No associated
Contact always
function
open
Contact always
No associated
Contact always
closed
function
2
of blocking
of blocking
3
7.6.19 FW: Firmware update
This menu page allows you to update the e.sybox firmware. For the
procedure see chapter 11.
7.6.20 - RF: Fault and warning reset
Holding down the + and – keys together for at least 2 seconds deletes
the history of faults and warnings. The number of faults present in the log
is indicated under the symbol RF (max 64).
The log can be viewed from the MONITOR menu on page FF.
7.6.21 - PW: Change password
The device has a password-enabled protection system. If a password is
set, the parameters of the device will be accessible and visible but it will
not be possible to change them.
When the password (PW) is "0" all the parameters are unlocked and can
be edited.
When a password is used (value of PW different from 0) all modifications
are blocked and "XXXX" is displayed on the page PW.
status
If the password is set it allows to navigate through all the pages, but at
open
any attempt to edit a parameter a pop-up appears, asking you to type in
the password. When the correct password is typed in the parameters are
closed
unlocked and can be edited for 10' after the last key is pressed.
If you want to cancel the password timer, just go to page PW and hold
down + and – together for 2".
Presence
In the case of
Output activa-
blocking errors the
tion in case of
contact closes
blocking errors
errors
Presence
In the case of
Output activa-
blocking errors the
tion in case of
contact opens
blocking errors
errors
Table 21: Configuration of the outputs
When the motor is
running the contact
closes
When the motor is
running the contact
opens