Franklin Electric SUBMONITOR CONNECT Manual De Instalación Y Funcionamiento Del Propietario página 19

Ocultar thumbs Ver también para SUBMONITOR CONNECT:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Mod
Menu / Parameter
RW
RC
bus
433
RW
N
Overvoltage
(level)
452
RW
N
Underpower
(enable)
453
RW
N
Underpower
(level)
418
RW
N
Current Unbalance
(enable)
419
RW
N
Current Unbalance
(level)
106
W
Y
Date
107
W
Y
108
W
Y
Time
109
W
Y
N/A
RW
N
Name Tag
Programming: Advanced Setup > Motor Protection > Current
Mod
Menu / Parameter
RW
RC
bus
Overload Menu
FLA/SFA Motor
403
RW
N
Trip Class
Range
Name
101 to 125; 110 (default)
0 - Off
1 - Fault and Alarm (default)
2 - Alarm Only
1 to 99;
SMS default = 65
Reduced Voltage SMS
default = 50
0 - Off
1 - Fault and Alarm (default)
2 - Alarm Only
1% to 50%; 5% (default)
MM/DD/YY
HH:MM:SS
16 characters maximum
Range
Name
1.0 A to 1000.0 A
5
10
20
30
S - Submersible Motor
Programming: Advanced Setup > Motor Protection > Current
This sets the percentage of nominal voltage that triggers
a fault when over voltage trip level is reached. For
example, setting a value of 110 means 110% of the nominal
voltage value will trigger a fault.
When set to Alarm Only or Fault and Alarm, this trips if
the measured kW is less than the kW trip point setting
(next menu item) continuously for a time that exceeds
the under power trip time setting. The trip time is set in
Advanced Setup > Motor Protection > Voltage >
Undervoltage > Time to Trip.
This sets the percentage of the calculated nominal power
level that triggers a fault when the trip level is reached.
For example, setting a value of 110 means 110% of the
nominal power value will trigger a fault. As the
percentage changes, the wattage setting is automatically
calculated.
When set to Alarm Only or Fault and Alarm, an alarm
triggers if the calculated average of the three line-to-line
currents exceed the user set nominal Current Unbalance
percentage (next menu item).
Trips if any of the 3 measured phase currents deviate from
the average current by a value greater than or equal to
the trip percentage setting. For example, setting a value
of 5 means 5% of current unbalance.
Sets the system date. Only the 3 least significant bytes
are used. From least to most significant byte: year, day,
month (0x00MMDDYY).
Sets the system time. Only the 3 least significant bytes
are used. From least to most significant byte: second,
hour, day (0x00HHMMSS).
The name tag identifies this SubMonitor Connect when
using communication protocols.
For surface motor applications, this should be set to the
FLA listed on the motor nameplate.
For submersible motor applications, set according to the
SFA listed in the Franklin AIM manual.
Sets the overload trip class. This follows the industry
2
standard I
t trip curve.
Surface Pump default = 10
Submersible Pump default = S
INSTALLATION AND SETUP
Description
Description
19