Franklin Electric SUBMONITOR CONNECT Manual De Instalación Y Funcionamiento Del Propietario página 30

Ocultar thumbs Ver también para SUBMONITOR CONNECT:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

OPERATION
Monitoring Functions
Advanced Setup Menu > View Menus
Mod
RW
RC
Display Name
bus
N/A
R
N
View Meter
227
R
N
View Events
228
229
230
231
R
N
N/A
View I/O Status
219
R
N
View System
to
222
R
N
232
View SW Versions Meter Device (234, 235)
to
245
30
Range
View Voltage
View Current
View Power
Insulation (in kΩ)
View Start History
View Power Loss Count
(Modbus 227)
View Motor Run Time
(Modbus 228, 229)
View Power-On Time
(Modbus 230, 231)
01/02 Status
Bluetooth MAC ID
Bluetooth Name
Bluetooth Key
Bluetooth Error
System Date (Modbus 219,
220)
System Time (Modbus 221,
222)
Serial Number
Model Number
Recovery Code
I/O Device (232, 233)
Display Device (236, 237)
I/O Boot LDR (238, 239)
Meter Boot LDR (240, 241)
Bluetooth Module (242, 243)
Gate Drive (244, 245)
Description
Use the read-only View Meter menus to see the current
readings for Voltage, Current, Power, and Insulation
Resistance.
Start History records starting events #1 through #25.
Each starting event records:
A-B Voltage
B-C Voltage
C-A Voltage
Min A-B Voltage
Min B-C Voltage
Min C-A Voltage
Line A Current
Line B Current
Line C Current
Peak Current
Power Factor
System State
HOA Mode
Motor State
Date
Time
Power Loss Count is a running total of the number of
recorded power losses (until reset).
Motor Run Time is a running total of time the motor is
running (until reset).
Power On Time is a running total of time the SubMonitor
Connect is powered up.
This shows if the Relay Output (01/02) is open or closed.
Bluetooth parameters are also displayed here. The
Bluetooth key is used to make a connection between the
SubMonitor Connect and a smart phone or other such
device.
Cycle power to clear a Bluetooth error.
This reads and shows the current Date, Time, Serial
Number, Model Number, and the Recovery Code.
There are no available Modbus addresses for Serial
Number, Model Number, and Recovery Code.
Recovery Code is used by Franklin Electric to recover a
forgotten password.
This menu shows the software version numbers for the
listed items.
Periods are implied after 2 and 4 decimal digits from the
right (10203 = v01.02.03).

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido