Franklin Electric SUBMONITOR CONNECT Manual De Instalación Y Funcionamiento Del Propietario página 42

Ocultar thumbs Ver también para SUBMONITOR CONNECT:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

COMMUNICATIONS
Modbus RTU Communication
Mod
R/W
RC
Address Name
Bus
300
R
N
Average Voltage
301
R
N
A-B Voltage
302
R
N
B-C Voltage
303
R
N
C-A Voltage
304
R
N
L-N Voltage
305
R
N
Frequency
306
R
N
Phase Order
307
R
N
Voltage Unbalance 0 to 100.0
308
R
N
A-B Min Voltage
309
R
N
B-C Min Voltage
310
R
N
C-A Min Voltage
311
R
N
Average Current
312
R
N
Phase A Current
313
R
N
Phase B Current
314
R
N
Phase C Current
315
R
N
Ground Current
316
R
N
Current Unbalance 0 to 100.0
317
R
N
Peak Current
318
R
N
Present Real
Power
319
R
N
Present Apparent
Power
320
R
N
Present Reactive
Power
321
R
N
Average PF
42
Choices/Range
The following ranges are scaled by a multiplier (shown in this table as multi = x.x). For
example, if a voltage of 100 V is reported by Modbus as 1000, the user has to multiply
the Modbus value by 0.1 for the actual value of the reading.
0 to 9000.0
multi
= 0.1
0 to 9000.0
multi
= 0.1
0 to 9000.0
multi
= 0.1
0 to 9000.0
multi
= 0.1
0 to 9000.0
multi
= 0.1
45.0 to 66.0
multi
= 0.1
0 - Undefined
1 - A-B-C
2 - A-C-B
multi =
0.1
0 to 1320.0
multi =
0.1
0 to 1320.0
multi=
0.1
0 to 1320.0
multi =
0.1
0 to 14000.0
multi
= 0.1
0 to 14000.0
multi
= 0.1
0 to 14000.0
multi
= 0.1
0 to 14000.0
multi
= 0.1
0 to 14000.0
multi
= 0.1
multi
= 0.1
0 to 14000.0
multi
= 0.1
-2000.0 to 2000.0
multi
= 0.1
-2000.0 to 2000.0
multi
= 0.1
-2000.0 to 2000.0
multi
= 0.1
-1.00 to 1.00
multi =
0.0 1
Description
Average voltage across all phases.
Phase A to Phase B voltage reading
Phase B to Phase C voltage reading
Phase C to Phase A voltage reading
Line-to-neutral voltage reading
Line frequency measurement
Phase Order
Voltage unbalance percentage
Minimum phase-to-phase voltage during the last start
Minimum phase-to-phase voltage during the last start
Minimum phase-to-phase voltage during the last start
Average current among all phases
Phase A current
Phase B current
Phase C current
Ground current
Current unbalance percentage
Peak inrush current during the last start
Real power in kW
Apparent power in kVA
Reactive power in kVAR
Power Factor

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido