Franklin Electric SUBMONITOR CONNECT Manual De Instalación Y Funcionamiento Del Propietario página 22

Ocultar thumbs Ver también para SUBMONITOR CONNECT:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

INSTALLATION AND SETUP
Programming: Advanced Setup > Motor Protection > Power
Mod
RW
RC
Display Name
bus
440
RW
N
Time to Trip
441
RW
N
Fault Reset Type
442
RW
N
Reset Retries
443
RW
N
Reset Delay
Voltage Unbalance Menu
444
RW
N
Trip/Alarm
445
RW
N
Unbalance Level
446
RW
N
Time to Trip
447
RW
N
Fault Reset Type
448
RW
N
Reset Retries
449
RW
N
Reset Delay
Phase Reversal Menu
450
RW
N
Trip/Alarm
451
RW
N
Phase Order
Voltage Loss Menu
487
RW
N
Fault Reset Type
488
RW
N
Reset Retries
489
RW
N
Reset Delay
Programming: Advanced Setup > Motor Protection > Power
Mod
RW
RC
Display Name
bus
Underpower menu
452
RW
N
Trip/Alarm
453
RW
N
Underpower Level 1 to 99; default = 50/65
454
RW
N
Underpower Delay 1 to 120; default = 2/3
22
Range
1 to 120; default = 10
0 - Manual
1 - Automatic (default)
1 to 10; default = 3
1 to 43,200; default = 900
0 - Off
1 - Fault and Alarm (default)
2 - Alarm Only
1% to 25%; default = 1%
1 to 120; default = 10
0 - Manual
1 - Automatic (default)
1 to 10; default = 3
1 to 43,200; default = 900
0 - Off
1 - Fault and Alarm (default)
2 - Alarm Only
0 - A B C (default)
1 - A C B
0 - Manual (default)
1 - Automatic
1 to 10; default = 3
1 to 43,200; default = 900
Range
0 - Off
1 - Fault and Alarm (default)
2 - Alarm Only
Description
Undervoltage Delay Time in seconds
Undervoltage Reset Method
When automatic reset is enabled, this sets how many
times to attempt resetting the fault.
The number of seconds between automatic resets.
Choose the type of response for when a Voltage Unbal-
ance is detected.
Percentage of voltage unbalance detected to cause a
fault condition.
Amount of time in seconds for the unbalanced voltage
situation to subside. If exceeded, then trigger the fault.
Choose the Voltage Unbalance reset method.
When automatic reset is enabled, this sets how many
times to attempt resetting the fault.
The number of seconds between automatic resets.
Choose the type of response for when a voltage phase
reversal condition is detected.
Phase Order
Choose whether the Voltage Loss fault reset is performed
manually or automatically.
When automatic reset is enabled, this sets how many
times to attempt resetting the fault.
The number of seconds between automatic resets.
Description
Underpower Protection Enable
Underpower Level Percentage
SMS default = 65
Reduced Voltage SMS default = 50
Underpower Delay Time in seconds
SMS default = 3
Reduced Voltage SMS default = 2

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido