Franklin Electric SUBMONITOR CONNECT Manual De Instalación Y Funcionamiento Del Propietario página 51

Ocultar thumbs Ver también para SUBMONITOR CONNECT:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Fault and Alarm Descriptions
Fault
Type
Displayed Text
Overload
Fault
OVERLOAD
FAULT
Over Current
Fault
OVERCURR
FAULT
Over Power
Fault or
OVERPOWER
Alarm
FAULT
Under Power
Fault or
UNDER-POWER
Alarm
FAULT
Insulation Check Fault
INSULATION
and
FAULT
Alarm
Over Voltage
Fault or
OVERVOLT
Alarm
FAULT
Under Voltage
Fault or
UNDERVOLT
Alarm
FAULT
Current Phase
Fault or
CURR UNBL
Unbalanced
Alarm
FAULT
Voltage Phase
Fault
VOLT LOSS
Loss
FAULT
Voltage Phase
Fault or
VOLT UNBL
Unbalanced
Alarm
FAULT
Cycle Fault
Fault
CYCLE FAULT
Locked Rotor
Fault
LCKD ROTOR
FAULT
Stall
Fault
STALL FAULT
Max Time to
Fault
START TIME
Start
FAULT
Out of
Fault
OUT OF CAL
Calibration
FAULT
PT100/PT1000
Fault
RTD TEMP FAULT Trips if the temperature measured by a PT100 or PT1000 exceeds the trip
Over Temp
Reverse Phase
Fault
PHASE ORDR
FAULT
No Current
Fault or
NO CURR FAULT Faults if there is no current for three seconds after a start.
Alarm
Unexpected
Alarm
UNEXP CURR
Current Flow
FAULT
Ground Fault
Fault
GROUND FAULT Trips if the vector sum of the 3 measured phase currents exceeds the
Description
Selectable Class 5-30, and S. Trips if the current integrator exceeds the
trip point.
Trips if the measured current is greater than the trip point setting for a
time that exceeds the over current trip time setting.
Trips if the measured kW is greater than the kW trip point setting
continuously for a time that exceeds the over power trip time setting.
Trips if the measured kW is less than the kW trip point setting
continuously for a time that exceeds the under power trip time setting.
Trips if the measured resistance of the motor windings is less than
insulation check resistance fault/alarm trip threshold.
Trips if the average of the 3 line-to-line voltages exceeds the nominal
voltage setting by the over voltage percentage setting continuously for a
time exceeding the over voltage trip time setting.
Trips if the average of the 3 line-to-line voltages is lower than the nominal
voltage setting by the under voltage percentage continuously for a time
exceeding the under voltage trip time setting.
Trips if any of the 3 measured phase currents deviates from the average
current by a value greater than or equal to the trip percentage setting.
Trips if the L-G voltage of any phase is more than 40% lower than the
average voltage.
Trips if any of the 3 measured line-to-line voltages deviates from the
average line-to-line voltage by a value greater than or equal to the
voltage phase unbalance trip percentage setting for a time exceeding the
voltage phase unbalanced trip time setting.
Trips if run command is triggered at a rate exceeding the start limit
divided by the limit period.
Trips if the current exceeds 300% of the calculated FLA setting for 0.5
seconds, the current is flat or increasing and the power factor is not
changing. This protection is active during the first ten seconds of
operation after a start.
Trips if the current exceeds 300% of the FLA for 0.5 seconds, the current is
flat or increasing and the power factor is not changing. This protection is
active after the first ten seconds of a start event and after the FLA has
been determined.
Trips ten seconds after current is detected following a contactor closure, if
the average current is above 200% of the FLA setting and still declining.
Trips if the measured peak inrush is outside the range of 400% to 1400%
of the FLA/SFA setting. This protection is only active during each start
sequence and for 10 seconds after every start.
temperature setting.
Trips if the phase order detected is different than phase order setting of
either A-B-C or
A-C-B.
Alarms if the starter detects current flow above a threshold of 0.2 A while
the starter is in the stopped state.
ground fault threshold setting.
MAINTENANCE
Troubleshooting
Default Setting
Class 5
On, 110%, 30 s
On, 125%, 10 s
On, 65%, 1 s
Off, 500 kΩ (Alarm),
200 kΩ (Fault)
On, 110%, 10 s
On, 90%, 10 s
On, 5%, 10 s
On, 60 VAC, N/A
Off, 1%, 10 s
Off
On
Off
Off
Off
Off
On
Off
Off
On, 1 A
51

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido