Programming: Advanced Setup > Communications
Mod
RW
RC
Display Name
bus
Modbus menu
N/A
Com Control
Write Access
Com Loss Fault
Com Loss Time
Baud Rate
Parity
Modbus Address
Bluetooth menu
N/A
Bluetooth
Programming: Advanced Setup > Timers
Mod
RW
RC
Display Name
bus
529
RW
N
Start Delay Enable Enabled
530
RW
N
Start Delay Time
(setting)
531
RW
N
Stop Delay Time
532
RW
N
Stop Delay Time
(setting)
533
RW
N
Min Off Time
534
RW
N
Min Off Time
(setting)
535
RW
N
Min Run Time
Enable
536
RW
N
Min Run Time
(setting)
Range
Enabled
Disabled (default)
Enabled (default)
Disabled
Enabled
Disabled (default)
1 to 120 seconds
(default = 10)
9600
19200 (default)
38400
57600
76800
115200
None; 1 Stop
Odd
Even
None; 2 Stop (default)
1 to 247; default = 247
Enabled (default)
Disabled
Range
(MT1311/MT2211 only)
Disabled (default)
1 to 43,200; default = 1
Enabled
Disabled (default)
1 to 43,200; default = 1
(All models)
Enabled
Disabled (default)
1 to 43,200; default = 1
Enabled
Disabled (default)
1 to 43,200; default = 1
Programming: Advanced Setup > Communications
Description
Use these setting to set up Modbus communications for
the SubMonitor Connect.
In Modbus communications, a computer or master
communication device issues commands to one of the
network nodes and processes responses. Other devices
on the network do not transmit data without a request
from the master computer, and do not communicate with
each other.
Choose Enabled to use Bluetooth communication for the
FE Connect mobile app.
Description
Enables or disables the Start Delay Time (for use with
Hand Mode and Auto Mode).
Sets the amount of start delay time in seconds.
Enables or disables the Stop Delay Time (for use with
Auto Mode only).
Sets the amount of stop delay time in seconds.
Enables or disables the Minimum Off Time (for use with
Hand Mode and Auto Mode).
Sets the amount of minimum off time in seconds.
Enables or disables the Minimum Run Time (for use with
Hand Mode and Auto Mode).
Sets the amount of minimum run time in seconds.
INSTALLATION AND SETUP
25