Franklin Electric SUBMONITOR CONNECT Manual De Instalación Y Funcionamiento Del Propietario página 48

Ocultar thumbs Ver también para SUBMONITOR CONNECT:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

COMMUNICATIONS
Modbus RTU Communication
Mod
R/W
RC
Address Name
Bus
515
RW
N
Soft Stop Voltage
Level
516
RW
N
Soft Start Inside
Delta
517
RW
N
Soft Start Motor PF
518
RW
N
D1 Type
519
RW
N
D1 Function
520
RW
N
D2 Type
521
RW
N
D2 Function
524
RW
N
D1/D2 Function
526
RW
N
Limit Sw Delay
527
RW
N
O1 Function
528
RW
N
O2 Status Level
529
RW
N
Start Delay Enable
530
RW
N
Start Delay Time
531
RW
N
Stop Delay Enable
532
RW
N
Stop Delay Time
533
RW
N
Min Off Time Enable 0 - Disabled (default)
534
RW
N
Min Off Time
535
RW
N
Min Run Time Enable 0 - Disabled (default)
536
RW
N
Min Run Time
48
Choices/Range
10 to 90; default = 70
0 - Disabled (default)
1 - Enabled
0.60 to 0.99; default = 0.80
multi = 0.01
0 - Normally Open (default)
1 - Normally Closed
0 - Auto Run (default)
1 - Permissive 1
0 - Normally Open
1 - Normally Closed (default)
0 - Shutdown (default)
1 - Permissive 2
0 - Auto Run/Shutdown
(default)
1 - Fill Mode - Low/High Float
2 - Drain Mode - Low/High Float
1 to 120; default = 30
0 - General Fault (default)
1 - Shunt Trip
1 to 99; default = 60
0 - Disabled (default)
1 - Enabled
1 to 43,200; default = 1
0 - Disabled (default)
1 - Enabled
1 to 43,200; default = 1
1 - Enabled
1 to 43,200; default = 1
1 - Enabled
1 to 43,200; default = 1
Description
Soft Stop Voltage Level percentage
When enabled, allows for soft starting of motors equipped with
inside delta setup.
Power Factor setting from Soft Start Motor Label
D1 Contact Type Setting
D1 Function Setting
D2 Contact Type Setting
D2 Function Setting
Intended use for D1/D2 connection
Limit Switch Delay Time in seconds
Output Relay O1 Function
Output Relay O2 Status Level Threshold
Enables the Start Delay time period (below) for use in Hand
Mode and Auto Modes
Sets the Start Delay time period in seconds.
Enables the Stop Delay (in Auto Mode only)
Sets the Stop Delay time period in seconds.
Enables the Minimum Off Time (for use with Hand Mode and
Auto Mode)
Sets the Minimum Off Time in seconds
Enables the Minimum Run Time setting (below) for use in Auto
Mode only.
Sets the Minimum Run Time in seconds

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido