Mod
Menu / Parameter
RW
RC
bus
Ground Fault Menu
424
RW
N
Trip/Alarm
425
RW
N
Current Level
No Current
426
RW
N
Trip/Alarm
Unexpected Current
427
RW
N
Trip/Alarm
Out of Calibration Menu
428
RW
N
Trip/Alarm
Max Start Time Menu
429
RW
N
Trip/Alarm
Programming: Advanced Setup > Motor Protection > Voltage
Mod
RW
RC
Display Name
bus
Overvoltage Menu
432
RW
N
Trip/Alarm
433
RW
N
Overvoltage Level 101 to 125; default = 110
430
RW
N
Nominal Voltage
431
434
RW
N
Time to Trip
435
RW
N
Fault Reset Type
436
RW
N
Reset Retries
437
RW
N
Reset Delay
Undervoltage Menu
438
RW
N
Trip/Alarm
439
RW
N
Undervoltage
Level
430
RW
N
Nominal Voltage
431
Range
Name
0 - Off
1 - Fault and Alarm (default)
2 - Alarm only
1 A to A; default = 1.0 A
0 - Off (default)
1 - Fault and Alarm
2 - Alarm only
0 - Off (default)
1 - Fault and Alarm
2 - Alarm only
0 - Off
1 - Fault and Alarm (default)
2 - Alarm only
0 - Off (default)
1 - Fault and Alarm
2 - Alarm only
Range
0 - Off
1 - Fault and Alarm (default)
2 - Alarm Only
120.0 to 7,200.0;
default = 208.0 multi = 0.1
1 to 120; default = 10
0 - Manual
1 - Automatic (default)
1 to 10; default = 3
1 to 43,200; default = 900
0 - Off
1 - Fault and Alarm (default)
2 - Alarm Only
75 to 99; default = 90
120.0 to 7200;
default = 208.0 multi = 0.1
Programming: Advanced Setup > Motor Protection > Voltage
Choose the type of response for ground fault current pro-
tection.
Amount of ground fault current that will trigger a fault
condition.
Choose the type of response for no current detected
when current is expected.
Choose the type of response for when unexpected cur-
rent is detected.
Choose the type of response when the measured peak
inrush current is outside of the range of 400% to 1400%
of the user-set FLA.
Choose the type of response for when the start time for
the motor is exceeded.
Overvoltage Protection Enable
Overvoltage Level Percentage
Nominal Voltage setting
Overvoltage Delay Time in seconds
Overvoltage Reset Method
When automatic reset is enabled, this sets how many
times to attempt resetting the fault.
The number of seconds between automatic resets.
Undervoltage Protection Enable
Undervoltage Level Percentage
Nominal Voltage setting
INSTALLATION AND SETUP
Description
Description
21