Section 3: Operation

Site Prep Verification

It is important that the generator is installed in such a way
that the airflow into and out of the generator is not
impeded. Verify that all shrubs or tall grasses have been
removed within 3 ft. (0.91m) of the intake and discharge
louvers on the sides of the enclosure. It is also important
that the generator is not subject to water intrusion. Verify
that all potential sources such as water sprinklers, roof
run-off, rain gutter down spouts and sump pump
discharges are directed away from the generator
enclosure.
DANGER
Automatic start-up. Disconnect utility power and
render unit inoperable before working on unit.
Failure to do so will result in death or serious injury.
Turn the generator OFF before performing maintenance.
Remove 7.5 Amp fuse, T1 and T2 battery charge fuses,
and disconnect battery cables to prevent accidental start
up. Disconnect the NEGATIVE (-) cable first, then
disconnect the POSITIVE (+) cable. When connecting
the cables, connect the POSITIVE cable first, the
NEGATIVE cable last.
WARNING

Side Compartment

Local codes may require this compartment to be locked.
A hasp is provided so the owner/operator can secure the
compartment with a padlock. Check local codes for side
compartment locking requirements.
B
C
Figure 3-1. Open Side Compartment
Owner's Manual for 60 Hz Air-cooled Generators

Main Circuit Breaker (Generator Disconnect)

This is a 2-pole breaker rated according to relevant
specifications. See "A" in

LED Indicator Lights

See "B" in
NOTE: Yellow LED may be on at the same time as either
the Red or Green LED.
(000191)
120V GFCI Outlet/15 Amp Breaker
(16-22 kW Only)
Some units are equipped with an external 15 Amp, 120
volt GFCI convenience outlet located in the top corner of
the compartment. See "C" in
When the generator is running, in the absence of utility
power, this outlet may also be used to power items
outside the home such as lights or power tools. This
outlet may also be used when utility power is present by
running the generator in manual mode.
This outlet does not provide power if the generator is not
(000182)
running. Do not use this outlet when the generator is in
Exercise mode. This outlet is protected by a 15 Amp
circuit breaker in the side compartment.

Generator Enclosure

The lid will be locked. A set of keys is attached to the
circuit breaker box door with a cable tie.
1.
2.
NOTE: The enclosed keys provided with this unit are
intended for service personnel use only.
000931
A
Figure 3-1.
Figure 3-1.
Green LED "Ready" light is on when utility is
present and the control panel button is in the AUTO
position. This also indicates when the generator is
running.
Red LED "Alarm" light is on when the generator is
OFF or a fault is detected. Contact an authorized
servicing dealer.
Yellow LED "Maintenance" light.
Cut the cable tie to remove the keys.
Use the keys to open the lid of the generator.
Section 3: Operation
Figure 3-1.
9