Chapter 3. Troubleshooting
3
Chapter
Troubleshooting
BICLUT03 (Published) Book specs- Dates: 20170301 / 20170301 / 20170301 Lang: ENG01 Applic: CLW
3.1. MilTouch
and MilTouch-EX
Messages that Can Occur on All Models
3.1.1.
Door Opened (1)
3.1.1.1.
operation at the current step.
Electrical Failure: If the door is not open, turn the machine Off. Do a check with the schematic
to find the cause of the error.
The controller stops the wash program and turns off all outputs. Correct the error condition, touch
the Cancel button, then press the Start button to resume the wash program.
Vibration Switch Tripped
3.1.1.2.
machine to the floor. Tighten or replace bolts that are loose or broken. Press the Start button to
resume operation at the current step.
The Load is Distributed Poorly: Do a check that there is enough water in the bath before the
extract step to allow the goods to spread around the basket. Press the Start button to resume
operation at the current step.
The Load is too Small: This machine works best when you fill it to the rated capacity of the
machine. Wash goods in full loads. Press the Start button to resume operation at the current step.
Too Much Water
3.1.1.3.
transducer detected a level more than twice as high as the configured high bath level. Touch the
Cancel button to silence the alarm and clear the error.
Pressure Switch SPOF is Actuated: Pressure switch SPOF (see schematics) actuated,
suggesting that the pressure transducer did not detect the bath level in the machine. Touch the
Cancel button to silence the alarm and clear the error.
Too Long to Fill (3)
3.1.1.4.
time. Increase the fill time if necessary.
Low Water Pressure: Do a check of the water pressure and volume to the machine.
PELLERIN MILNOR CORPORATION
—The Door Opened: Close the door. Press the Start button to resume
—The Machine is not Anchored: Check the bolts that hold the
—Bath Level is More Than Twice Configured High Level: The pressure
—Fill Time Configured too Short: Do a check of the configured fill
44
Error Messages