Gtec Saturn Manual Del Usuario página 75

Ocultar thumbs Ver también para Saturn:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Separate bypass on separate lines:
When the separate bypass option is present, protective devices should be placed on both the main power supply line and the
bypass line.
Note: The neutral of the input line and that of the bypass are commoned inside the equipment, therefore they must refer to the
same potential. In case the two power supplies were different, an isolation transformer would be necessary on one of the
inputs.
CPS with no modification of the neutral regime and with separate bypass input
CPS with separate bypass input connected to an independent power supply line
CPS with separate bypass input connected to an independent power supply line
connected to an independent power supply line
and with input galvanic isolation
and with output galvanic isolation