Configurations which can be modified by means of configuration software available at service centres are listed in the following
table.
FUNCTION
Operating mode
Output voltage
Output nominal frequency
Autorestart
Auto power off
Buzzer Reduced
EnergyShare off
Timer
Autonomy limitation
Maximum load
Bypass Synchronization speed
External synchronization
External temperature
Bypass mode
DESCRIPTION
Selects one of five different operating modes
Selects the rated output voltage
(Phase - Neutral)
Selects the rated output frequency
Waiting time for automatic power-on after the return of mains
Automatic CPS power-off in battery operation mode if the
charge is lower than 5%
Selects the audible alarm operating mode
Selects the auxiliary socket operating mode
Programmed CPS power on/off (daily)
Maximum battery operation time
Selects the user overload limit
Selects the synchronisation speed of the inverter to the bypass
Selects the source of synchronisation for the inverter output
Activates reading of the external temperature probe
Selects the mode of use of the bypass line
96
voltage
line
DEFAULT
ON LINE
230V
50Hz
5 sec.
Disabled
Reduced
Always connected
Disabled
Disabled
Disabled
1 Hz/sec
From bypass line
Disabled
Enabled /
High sensitivity