ATTERY LOW
During battery operation, when autonomy is down to an estimated 10 minutes, before the deep discharge protection cuts in, the
CPS emits an acoustic signal to warn of the imminent interruption to the load (approximately 10 minutes after the warning).
E
XTERNAL PROTECTION DEVICES

CIRCUIT BREAKER

When setting up the power supply line, install a circuit breaker with trip curve C (or D depending on the type of load) upstream
from the CPS, as indicated in the following table:
CPS model
20kVA
30kVA
* In the case of a non-linear load, oversize the neutral line N correctly after site assessment.
If the protection device upstream of the CPS interrupts the neutral conductor, it must also interrupt all the phase
conductors at the same time (quadripolar switch).
Normal fuses (gL-gG)
Magnetothermal switches (C curve)
Ultrarapid fuses (GF)
Automatic external protection devices*
Mains input
63A
80A
Output protections (recommended selectivity values)
Separate bypass input
In (Nominal current)/7
In (Nominal current)/7
In (Nominal current)/3
77
63A
80A