➢ After a few seconds, check that the display is turned on and that the CPS
enters STAND-BY mode.
If an error message appears on display indicating a wrong cyclic sense of the input phases, perform the following
operations:
▪
Open all the input and output isolators
▪
Wait for the display to turn off
▪
Open the battery fuse holders
▪
Open all the protections upstream the CPS
▪
Remove the protective panel covering the input terminal board
▪
Correct the position of the input wires so that the cyclic sense of the phases is respected.
Only if the separate bypass option is present: check which terminal board (input and/or bypass) the code error shown
on display corresponds to (see the "Alarm codes" paragraph); correct the position of the wires following the indications
on the terminal board.
▪
Close the protective panel again
▪
Repeat the preliminary operations given in the previous page.
➢ Press the
access the start-up menu. Press "YES" when requested to confirm. press
for a few seconds. Make sure that the CPS enters ON-LINE mode and that
the load is on the inverter.
➢ Open the input isolator (SWIN) and wait for a few seconds. Check that the
CPS enters "battery working" mode and that the load is still powered
correctly. You should hear a beep about once every 7 seconds.
➢ Close the input isolator (SWIN) and wait for a few seconds. Make sure that
the CPS is not on "battery working" mode anymore and that the load is still
powered correctly by the inverter.
➢ To set up Date and Time, access menu 8.6.7 (see "Menu display"). Use
direction buttons (
) to set up the desired value, and the confirm button
↑↓
(
next menu. To save the new set up, return to the previous menu by
pressing the
button.
button to
to confirm and wait
) to proceed to the
88