Special Functions
R R e e s s e e t t t t o o F F a a c c t t o o r r y y S S e e t t t t i i n n g g s s : : From the H H O O M M E E screen, press and hold the U U P P / / D D O O W W N N / / N N E E X X T T buttons at
the same time for 3 seconds. A confirmation screen (Are you sure?) appears in the display. Choosing
Y Y E E S S restores all programmable parameters to factory default settings (fault history is NOT cleared).
Choosing N N O O reverts back to the H H O O M M E E screen.
Factory Default Settings:
•
MAX AMPS = 1.0 A
•
TRANSDUCER RANGE = 200 PSI
•
UNDERLOAD SENSITIVITY = 65%
•
SYSTEM RESPONSE = Slow
•
DRAWDOWN = 5 PSI
•
SETPOINT 1 = 0 PSI. The Drive will run 5 seconds after SETPOINT 1 is adjusted above 0 PSI and N N E E X X T T
button is pressed. If the screen times out, the setting is not saved and the drive will not run.
NOTE: Setting S S E E T T P P O O I I N N T T 1 1 to 0 PSI causes the drive to enter the IDLE state.
•
SETPOINT 2 = 0 PSI. SETPOINT 2 being set above 0 PSI is not required for product to operate
M M A A N N U U A A L L S S T T O O P P M M o o d d e e : : From the H H O O M M E E screen, press and hold U U P P / / D D O O W W N N buttons together for 2 sec-
onds to manually place the drive in S S T T O O P P mode. The display shows S S T T O O P P in the upper right corner of
the H H O O M M E E screen where R R U U N N / / S S T T O O P P status is shown (same as placing a jumper on the R R U U N N / / S S T T O O P P input
terminal).
When activated, M M A A N N U U A A L L S S T T O O P P displays centered at bottom of H H O O M M E E screen where the motor speed
(Hz) and output current (A) readouts were displayed.
Pressing the U U P P / / D D O O W W N N buttons again for 2 seconds removes the drive from manual stop mode.
DRIVE CONFIGURATION
Menu Settings
33