Default
Parameter
Value
Broken Pipe
10
Minutes 1 to 60
Delay
Broken Pipe
25
Pressure
Minimum
SUB: 3
Seconds 0 to 6000
Off Time
CEN: 10
Underload
Underload
Mode Select
Underload
59
Frequency
Underload
65
Level
Underload
Smart Reset Minutes
Off Time
Underload
SUB: 3
Seconds 0 to 3000
Prime Time
CEN: 120
Over
Pressure
20
Offset
PT100
Disabled
Enable
PT100 Alarm
100
Limit
PT100 Fault
125
Limit
Range
Units
0 to (0.95*Sensor
PSI
Range)
•
Disabled
N/A
•
Underload
(Low Frequency
Limit) to (High
Hz
Frequency Limit)
%
25 to 95
•
Smart Reset
•
5 to 1440
Manually
10 to ((Sensor
Range) - GREATER
OF (Pressure Set-
PSI
point 1 or Pressure
Setpoint 2))
•
Enabled
N/A
•
Disabled
40 to (PT100 Fault
Celsius
Limit)
(PT100 Alarm Lim-
Celsius
it) to 150
Set Parameter Via:
Program-
Mobile
DIP
ming
App
Switch
No
No
Yes
No
No
Yes
No
No
Yes
No
No
Yes
No
No
Yes
No
Yes
Yes
No
Yes
Yes
No
No
Yes
No
No
Yes
No
No
Yes
No
No
Yes
No
No
Yes
SPECIFICATIONS
Programming Defaults
Change
while
Description
Running
Sets the amount of time the
drive must run before broken
No
pipe protection will stop the
motor.
Sets the pressure that the sys-
tem must be below for broken
No
pipe protection to stop the
motor.
Set the minimum time the drive
must be off before running
No
again.
Enables or disables Underload
No
protection
Sets speed at which drive must
run for underload detection to
No
trip.
Sets underload sensitivity
Yes
Sets time for drive to restart
after Underload condition.
Smart reset doubles time if
Yes
underload occurs within 180
seconds of running.
Sets the time before underload
protection is active upon
No
startup
Sets the pressure offset from
pressure setpoint to indicate
system overpressure. Ex. Set-
Yes
point of 50 and over pressure
offset of 20 will stop system
from going above 70 PSI.
Enables or disables the PT100
Yes
protection
Sets the alarm limit of the
Yes
PT100
Yes
Set the fault limit of the PT100
57