MAINTENANCE
Troubleshooting
Codes
Fault
F F 3 3 7 7
Fan Speed Fault •
F F 3 3 8 8
Internal Over
Temperature
F F 3 3 9 9
RTD Device
Missing
F F 4 4 1 1
MultiDrive
Sensor
Mismatch
F F 4 4 2 2
MultiDrive
Firmware
Mismatch
F F 4 4 3 3
MultiDrive
Comm Fault
46
Possible Causes
One or more of the internal
fans are not working
•
Airflow is impeded
•
High ambient temperature
•
Drive is in direct sunlight
•
Airflow is impeded
•
PT100 Select is set to "En-
abled" and no RTD device is
connected to the drive.
•
Drives using the built-in Multi-
Drive function are configured
with pressure sensor types that
do not match
•
Drives using the built-in Multi-
Drive function have firmware
versions that are not matched
•
Improper MultiDrive cable
connection
•
MultiDrive cable is damaged
Corrective Action
•
Check fan connections to the Control Board.
•
Fan blocked or inoperable, ambient above 104 °F (40 °C), di-
rect sunlight, air flow channel blocked
•
Replace internal stirring fans or relocate drive as necessary
•
Remove debris from fan intake/exhaust
•
The drive has exceeded max rated internal temperature of
176 °F (80 °C), and needs to drop below 167 °F (75 °C) to
restart
•
Replace fan or relocate drive as necessary
•
Remove debris from fan intake/exhaust
•
Switch PT100 Select to "Disabled"
•
Connect the RTD device to the drive
•
Drives using the built-in MultiDrive function must have
matching pressure sensor types, either a traditional pressure
sensor or a pressure transducer.
•
If both drives are configured with a pressure transducer, the
transducers must both be PSI type or bar type.
•
Firmware version of one or more drives must be updated to
a matching firmware version using the SubDrive Connect Plus
mobile app.
•
Check MultiDrive cable connections
•
Replace MultiDrive cable
•
Check dip switch setting for terminating resistor.