Franklin Electric SDCP-SUB0723 Manual Del Usuario página 44

Ocultar thumbs Ver también para SDCP-SUB0723:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

MAINTENANCE
Troubleshooting
Codes
Fault
F F 6 6
Short Circuit
F F 7 7
Overheated
Drive
F F 8 8
Over Pressure
F F 9 9
Internal PCB
Fault
F F 1 1 2 2
Overvoltage
F F 1 1 4 4
Broken Pipe
F F 1 1 5 5
Phase
Imbalance
F F 1 1 9 9
Communication
Fault
44
Possible Causes
When fault is indicated imme-
diately after power-up, short
circuit caused by a shorted
connection, defective cable,
splice, or motor
High ambient temperature
Direct sunlight
Obstruction of airflow channel
Measured pressure exceeds
setting
A fault was found internal to
drive
High line voltage
Internal voltage too high
Broken pipe or large leak is de-
tected in the system
Drive runs at full power for 10
minutes without reaching pres-
sure setpoint
Large water draw, such as a
sprinkler system, does not al-
low system to reach pressure
setpoint
Broken Pipe Pressure setting is
higher than the active Setpoint
pressure setting
Motor phase currents differ by
20% or more.
Motor is worn internally
Motor cable resistance is not
equal
Cable connection between
Control Board and Power
Board is loose or disconnected
Internal circuit failure
Corrective Action
Amperage exceeded 25 amps on DC test at start or SF amps
during running
Incorrect output wiring, phase to phase short, phase to
ground short in wiring or motor
If fault is present after resetting and removing motor leads,
replace drive
The drive has exceeded max rated temperature, needs to
drop below 167 °F (75 °C) to restart
Fans blocked or inoperable, ambient above 104 °F (40 °C),
direct sunlight, air flow channel blocked
Replace fans or fan module; or relocate drive as necessary
Remove debris from fan intake/exhaust
Troubleshoot system to locate reason for high pressure
Contact your Franklin Electric Service Personnel
Unit may require replacement. If problem persists, note the
sub-fault number on the display before contacting the FE
Service Personnel.
Line voltage high, greater than approximately:
- 290 VAC (normal 230 operating range = 190 to 260)
- 600 VAC (normal 460 operating range = 380 to 520)
Check incoming power connections and correct or tighten
terminals if necessary
If line voltage is stable and measured below 260 VAC and
problem persists, contact your Franklin Electric Service
Personnel.
Check system for large leak or broken pipe
If the system contains a sprinkler system or is being used to
fill a pool or cistern, disable the Broken Pipe Detection
Adjust the Broken Pipe Pressure setting to a value lower than
any active Setpoint pressure settings.
Check resistance of motor cable and motor windings.
Phase imbalance and loss of phase may indicate similar
issues.
Check cable connection between Control Board and Power
Board. The cable connection on the control board is located
on the back side of the control board.
If problem persists, unit may require replacement. Contact
your supplier.

Publicidad

Tabla de contenido
loading

Tabla de contenido