Electrical installation/Automatic mode
In selecting the wiring leads, it
is important to meet the wiring
regulations laid down in VDE
0100 (see Safety warnings on
page 20). The following applies
to wiring presence detectors:
Section 6 of VDE 0100 520 per-
mits the use of a multiple-
COM 1
L
N
P S N
COM1
L L'
conductor cable containing
both the mains-voltage wires
as well as the control lines (e.g.
NYM 5 x1.52) for the wiring bet-
ween sensor and electronic bal-
last. The mains supply lead must
be no greater than 10 mm in dia-
meter. The clamping range of
COM 2
L
N
P
COM 1 AP
L
N
L'
L
S
P
P N
N
- 22 -
the mains terminal is designed
for a maximum of 2 x 2.5 mm
When installing the surface-
mounting version, connect a
circuit breaker (16 A) on the
line side.
DIM
L
N
P S N
DIM
L L'
1-10V
max. 100 mA
L
N
P
2
.
L
N
1-10V
+ –