Functions – Settings by DIP switch
COM 1 + COM 2
DIP 1
Normal mode / Test mode (NORM / TEST)
Test mode has priority over all
other settings on the presence
detector and serves the purpose
of checking for proper working
order as well for testing the de-
tection zone. Irrespective of am-
DIP 2
Semi-automatic mode (MAN) / fully automatic mode (AUTO)
Semi-automatic mode: (MAN)
The light now only switches
'OFF' automatically. Light is
switched 'ON' manually. Light
must be requested using the
Fully automatic mode: (AUTO)
The light automatically switches
'ON' and 'OFF' in relation to
brightness when someone is
present. Light can be switched
'ON' and 'OFF manually at any
time. This temporarily interrupts
DIP 3
Button/switch
Tells the sensor how to interpret
the incoming signal. Assigning
external buttons/switches allows
you to operate the detector as a
semi-automatic unit and over-
ride it manually at any time.
DIP 4
'ON'/'ON'-'OFF' button
In the 'ON'-'OFF' setting, the light
can be switched 'ON' and 'OFF'
manually at any time (except in
pulse mode: no manual 'OFF').
DIM
DIP 5
Constant light 'ON'/'OFF'
Provides a constant level of
brightness. Detector measures
the prevailing level of daylight
and activates sufficient artificial
light to achieve the required lev-
bient light level, the presence
detector activates the light to
stay 'ON' for approx. 8 sec. in
response to movement in the
room (blue LED flashes when
movement is detected). All user-
button and stays 'ON' for the
time set at the potentiometer.
(pressing twice switches 'ON' for
4 hours).
the automatic switching func-
tion. Irrespective of the settings
selected, light stays 'ON' for 4
hours after manually pressing
the button twice or switches
'OFF' after manually pressing the
■
Operation either by button
or switch
■
Several buttons possible on
one control input
■
Only use illuminated pushbut-
ton with neutral conductor
connected
In the 'ON' setting, light can no
longer be switched 'OFF' manu-
ally. The stay-'ON' time starts
from the beginning again each
el of brightness. As daylight
changes, the switched-in artifi-
cial lighting component is ad-
justed accordingly. In addition to
the daylight component, artificial
- 24 -
selected potentiometer settings
apply in normal mode. The pres-
ence detector can also be set by
means of the blue LED without
any load connected.
button once. Pressing the but-
ton before the 4 hours elapse
returns the Presence Control IR
Quattro to the normal operating
mode.
■
Cable length between sensor
and switch < 50 m
time the button is pressed.
light is also switched 'ON' and
'OFF' in relation to whether or
not persons are present.