6. Installation Checkout
Turn ON the water supply to the valve.
Test for Leaks Without an Interface
Disconnect the power from the valve.
Connect the jumper to the valve, then reconnect the power to the valve.
Wait 10 seconds for the valve to initialize; the outlets will activate.
Check all connections for leaks.
Disconnect the power, then remove the jumper.
Reconnect the power to the valve.
Test for Proper Operation (Requires an Installed Interface)
Prompt interface: Press the power icon. The interface screen should be illuminated.
Mode interface: Press one of the icons to turn ON the interface.
If not already completed, refer to the digital interface Homeowners Guide to set up the interface.
NOTE: For more information about using the digital interface, refer to the digital interface Homeowners Guide.
Use the interface to turn ON the water outlets.
Check all connections for leaks, and make adjustments as needed.
Verify that the water flow is sufficient for your showering needs.
Exercise the Valve (Requires an Installed Interface)
NOTE: Recently installed or infrequently used valves should be exercised before setting the maximum temperature.
NOTE: The maximum water temperature to the outlets is limited to 120°F (49°C). The valve will automatically shut down
if the temperature exceeds 120°F (49°C).
Verify that the hot and cold water supply lines are connected to the appropriate valve inlets.
Prompt interface: Press the up and down arrow icons to adjust the temperature from cold to hot and back to cold
several times, pausing for 30 seconds at each extreme.
Mode interface: Turn the outside ring to adjust the temperature.