Descargar Imprimir esta página

Erreka VIVO-D103 Manual Del Instalador página 57

Cuadro de maniobra para el accionador izar
Ocultar thumbs Ver también para VIVO-D103:

Publicidad

Idiomas disponibles

Idiomas disponibles

Problem
The panel does not work and
no LED indicator comes on
The motor only works at slow
speed
The motor does not work,
DL8, DL9 and DL10 lit up
DL2 lit up
DL1 off when operating the
control devices
The motor does not work,
DL8, DL9 and DL10 lit up
DL2 lit up
DL1 lights up when pressing ST1,
ST2 and DL11 and DL12 light up
The motor does not work,
DL8, DL9 and DL10 lit up
DL2 lit up
DL1 lights up when pressing ST1,
ST2, and DL11 and DL12 remain off
The leaf does not reach the
stopper
The leaf does not reach the
stopper
DL2 off, DL6 on
The gate does not make the
programmed speed changes
The gate opens but does not
close
DL2 off
Cause
Main circuit breaker SW1 in "OFF"
Absence of panel power supply
Electronic cutout F1 blown
Transformer or switchboard failed
Absence of panel power supply,
with the panel running off the
battery
The travel of the gate has only been
recorded at slow speed.
The control devices signal does not
reach the panel
Motor cutouts F2 and/or F3 blown
Motor connections
M o t o r , t r a n s f o r m e r o r p a n e l
defective
Ends of travel poorly connected or
constantly activated (DL3 or DL4
off)
Panel failed
Opening programming incorrect
Limit switches wrongly adjusted
Motor sensitivity very high, not
suitable for the weight of the gate
Crankshaft incorrectly positioned
The photocell has detected an
obstacle
T h e o p e r a t i o n h a s n o t b e e n
properly memorised
Absence of panel power supply,
with the panel running off the
battery
There is a safety item activated (in
closing)
MAINTENANCE AND DIAGNOSIS OF FAILURES
Solution
Place SW1 in "ON"
Re-establish the power supply
Replace F1 using another fuse of the
same value and investigate the cause
of failure of F1
Call the technical service
Re-establish the power supply
Programme the travel as described in
"Programming of the opening and
closing travel" on page 49.
C h e c k t h e k e y d e v i c e s a n d t h e
connections
Replace F2 and/or F3 with another
c u t o u t o f t h e s a m e v a l u e a n d
investigate the cause of failure of F1/F3
Check connections
Call the technical service
Check the limit switch
Call the technical service
Carry out the programming correctly
Adjust limit switches
Adjust motor sensitivity
Correct the slant and position of the
crankshaft
Check the possible obstacles
Memorise the operation again with
the gate closed
Re-establish the power supply
Remove possible obstacles
VIVO-D103 / ADB30 Control Panel
53