Auto test:
The menu item auto test makes it possible to
test the automatic program sequence in fast
mode and to monitor it on the display.
Abbreviations indicate which of the facility's
consumers are currently active during a pro-
gram section.
If you press the button
•
between aeration on and aeration off is
passed through.
Use the button
•
next program step.
Use the button
•
sediment extraction on expiry of the next
settling phase.
Use the button
•
test anew.
Use the button
•
test.
EN16
, the interval
to call the respective
to induce an automatic
to start the function
to quit the function
Operating instructions AquaCycle 900
Conditions for the automatic test:
You can only activate the different function
tests, if the water levels in the individual stages
that are required for this have been reached.
Automatic sediment extraction: Only possible if
the minimum fill level has been reached in the
corresponding stages.
Automatic filter backflushing: Only possible if
the maximum fill level has not been reached in
stage 1 and no automatic filter backflushing has
taken place within the last 5 minutes and/or if
the automatic filter cleaning process is not blo-
cked.
Pump stage 1 and pump stage 2: The pumps
only switch on if the stage in which the pump is
located has reached the minimum fill level and
the stage into which the water is to be pumped
has not reached the maximum fill level.
050608