SMA Solar Technology AG
Name
Voltage monitoring of lower min.threshold as RMS
value for tripping time
Frequency monitoring upper minimum threshold
(Underfrequency)
Frequency monitoring lower maximum threshold
(Overfrequency)
Frq. monitoring upper min. threshold trip. time (Un-
derfrequency, maximum time)
Frq. monitoring lower max. threshold trip. time
(Overfrequency, maximum time)
Installation Manual
7 Commissioning
Value/range
Default value
0.1 s to 60 s
44 Hz to 60 Hz
50 Hz to 66 Hz
0.1 s to 1000 s
0.1 s to 1000 s
STP33-62-US-41-IA-xx-14
0.16 s
59.3 Hz
60.5 Hz
0.16 s
0.16 s
57