Total harmonic distor-
tion of the output cur-
rent with total harmonic
distortion of the AC
voltage <2%, and AC
power >50% of the
rated power
Maximum residual out-
put current
Duration of the maxi-
mum residual output
current
Current unbalance
Line synchronization
characteristics
Rated grid frequency
Operating range at AC
grid frequency 60 Hz
Limits of accuracy of
voltage measurement
Limits of accuracy of
frequency measure-
ment
Limits of accuracy of
time measurement at
nominal trip time
Limits of accuracy of
current measurement
Limits of accuracy of
power (active/reactive)
measurement
Limits of accuracy of
power factor measure-
ment
Limits of accuracy of
time measurement
Installation Manual
STP 33-US-41
< 3 %
440 Apeak
26 ms
0.06 %
Method 2
60 Hz
54 Hz to 66 Hz
2% of the AC voltage
±0.1 Hz
± 0.1 %
1% of the AC current
5% of the nominal AC
power
0.01
0.001 s
STP 50-US-41
< 3 %
440 Apeak
26 ms
0.07 %
Method 2
60 Hz
54 Hz to 66 Hz
2% of the AC voltage
±0.1 Hz
± 0.1 %
1% of the AC current
5% of the nominal AC
power
0.01
0.001 s
STP33-62-US-41-IA-xx-14
10 Technical Data
STP 62-US-41
< 3 %
440 Apeak
26 ms
0.09 %
Method 2
60 Hz
54 Hz to 66 Hz
2% of the AC voltage
±0.1 Hz
± 0.1 %
1% of the AC current
5% of the nominal AC
power
0.01
0.001 s