Thawing
4.8
The thawing cycle is only available if the load managed by the K4 output is the thawing heater (u1 = 2).
Access the SPECIAL CYCLES menu from the
displayed, from which you can select the quantity of the product to be thawed using the
next time that the
key is pressed the cycle starts.
The defrosting cycle is managed on the basis of the amount of product to be defrosted that is loaded into the unit in
relation to the maximum quantity specified by the manufacturer. To keep it simple, the load quantities that can be
selected are divided into three bands, for each of which the controller will load three different sets of predefined
parameters, in accordance with the following scheme:
Load band
LIGHT LOAD
MEDIUM LOAD
FULL LOAD
These three parameters will be used to control the working cabinet setpoints and the duration of the thawing cycle,
equally divided into five phases following on from each other as shown.
- Phase 1 working setpoint = initial setpoint
- Phase 2 working setpoint = phase 1 setpoint + [(initial setpoint – final setpoint) / 4]
- Phase 3 working setpoint = phase 2 setpoint + [(initial setpoint – final setpoint) / 4]
- Phase 4 working setpoint = phase 3 setpoint + [(initial setpoint – final setpoint) / 4]
- Phase 5 working setpoint = final setpoint
key and select THAWING: at this point the start screen is
Initial cabinet setpoint
r25
r26
r27
14
Final cabinet setpoint
r28
r29
r30
and
keys. The
Cycle duration
r32
r33
r34
EN