ALARMS
7
Alarms
7.1
The alarms will be displayed on the Home page if the effect is to interrupt or to prevent the activation of the cycle. If
they are such as to allow the continuation of the cycle in progress they will instead take the place of the "cycle
progress bar" until they disappear.
The table below lists the various alarms.
Code
Description
Clock error.
To correct:
-
RTC
Main results:
-
-
Cabinet probe error.
To correct:
-
-
-
-
Main results:
-
CABINET PROBE
-
-
-
-
-
-
-
re-set the date and time.
the device will not save the date and time an HACCP alarm occurred.
the alarm output will be activated.
check the value of parameter P0
check the integrity of the probe
check the device-probe connection
check the cabinet temperature.
if the error occurs during "stand-by", it will not be possible to start up an operating
cycle
if the error occurs during blast chilling or blast freezing, the cycle will continue with the
compressor in continuous mode
if the error occurs during conservation, the compressor will operate according to
parameters C4 and C5 or C9
if the error occurs during a thawing cycle, the cycle will be interrupted
the minimum temperature alarm will never be activated
the maximum temperature alarm will never be activated
the door heaters will never be switched on
the alarm output will be activated
30