Take care that the drained refrigerant will not cause any
danger. In doubt, one person should guard the outlet. Take
special care that drained refrigerant will not float back
into the building.
● Evacuate the refrigerant circuit.
● Purge the refrigerant circuit with nitrogen for 5 min.
● Evacuate again.
● Fill with nitrogen up to atmospheric pressure.
● Put a label on the equipment that the refrigerant is re-
moved.
e) Disposal
● Ensure sufficient ventilation at the working place.
● Remove the refrigerant. If the recovery is not required by
national regulations, drain the refrigerant to the outside.
Take care that the drained refrigerant will not cause any
danger. In doubt, one person should guard the outlet. Take
special care that drained refrigerant will not float back
into the building.
● Evacuate the refrigerant circuit.
● Purge the refrigerant circuit with nitrogen for 5 min.
● Evacuate again.
● Cut out the compressor and drain the oil.
Transportation, marking and storage for units that em-
ploy flammable refrigerants
Transport of equipment containing flammable refrigerants
Attention is drawn to the fact that additional transporta-
tion regulations may exist with respect to equipment con-
taining flammable gas. The maximum number of pieces of
equipment or the configuration of the equipment, permit-
ted to be transported together will be determined by the
applicable transport regulations.
Marking of equipment using signs
Signs for similar appliances used in a work area generally
are addressed by local regulations and give the minimum
requirements for the provision of safety and/or health
120