Technical data
6)
Inputs
6)
Outputs
Switching outputs OSSDs
Switching voltage
(active, U
)
eff
Switching voltage
(inactive)
Switching current
Leakage current
Load capacity
Switching sequence
Load inductance
5)
Applies to the voltage range between -30 V and +30V.
6)
As per IEC 61 131-2
7)
In case of fault (0-V cable open circuit) the max. leakage current flows in the OSSD cable.
The downstream controller must detect this status as LOW. A safe PLC (Programmable Logic Con-
troller) must be able to identify this status.
8)
The maximum rated load inductance is higher with lower switching sequence.
y [H]
18.00
16.00
14.00
12.00
10.00
8.00
6.00
4.00
T
= 55 °C
A
2.00
0.00
0.00 0.50 1.00 1.50 2.00 2.50 3.00 3.50 4.00 4.50
Reset button
External device monitoring
Deactivate reset button
Deactivate external device monitoring
4 receiver inputs
4 sender outputs
2 PNP semiconductor, short-circuit pro-
5)
tected
, cross-circuit monitored
6)
HIGH
17.5 V
6)
LOW
7)
Depending on load inductance
8)
T
= 25 °C
A
Operating Instructions
L 4000 system
24 V
28.8 V
1.3 V
0.5 A
0.3 mA
2.2 µF
1.9 H
x [Hz]
8010009/TI69/2009-11-26