elobau eloFlex 471EFR2D14K Serie Manual Del Usuario página 6

Unidad de control de seguridad
Ocultar thumbs Ver también para eloFlex 471EFR2D14K Serie:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

eloFlex 471EFR
Control outputs 1-4
Input
 Safety input 1
 Safety input 2
 Safety input 3
 Safety input 4
 Ready for operation
 ERROR
 as for safety output 1
 as for safety output 2
 as for safety output 3
 as for safety output 4
There is no input assignment when selecting Ready for operation, Error, or
Safety outputs. The switch-on/switch-off delay time of between 0.0 s and
99.9 s for the outputs can be set in 0.1 second intervals.
LED displays
Operating time
The operating time is the maximum time permitted on a sensor between actu-
ation of both sensor contacts.
For two-hand control, this is the maximum time that may elapse between the
actuation of the two sensors.
If OR logic is configured, it is sufficient that an assigned safety input is correctly
actuated. If a delay time error is detected at another assigned safety input, the
assigned safety output is still switched on.
Safe condition
The safety outputs are opened or with high resistance.
8
Technical specifications
See „Technical specifications" from page
9
Installation
Danger of electrocution!
Ensure that the safety evaluation unit is installed and put into
operation only by specially trained, authorized personnel.
Danger
NOTE ON INSTALLATION
The unit is designed for heat dissipation by convection. A mini-
mum distance of 3 cm above and below the device is required for
heat dissipation. Ensure that sufficient ventilation is present.
In particular, ensure that the wiring does not prevent convection.
The device may be installed horizontally (Fig. 1) and vertically
(Fig. 2). For vertical installation, the maximum permissible ambi-
ent temperature is reduced by 10 °C. For optimum heat dissipa-
tion in the horizontal installation position, we recommend
maintaining a distance of approx. 1 cm between the devices.
Installation positions, see Fig. 1 and Fig. 2
Art.-Nr./Art. No./Réf./N° art/N° art.: 9010008B01M
Logic
Switch-on/
switch-off delay
 AND
 OR
 NAND
, s
 NOR
 XOR
 XNOR
 NOT
, s
LED a
Operational readiness ("Ready")
LED b
Fault ("Error")
LED c
Safety input 1 ("I 1")
LED d
Safety input 2 ("I 2")
LED e
Safety input 3 ("I 3")
LED f
Safety input 4 ("I 4")
LED g
Safety output 1 ("O 1")
LED h
Safety output 2 ("O 2")
LED i
Safety output 3 ("O 3")
LED j
Safety output 4 ("O 4")
19.
Version/Version/Version/Versione/Versión: 1.5
in s
t
ON
___
t
OFF
Fig. 1
- Ensure that the specified external fuse
page
19) is installed and used. This serves to protect the device or the relay
contacts.
- Snap the safety evaluation unit onto a top-hat rail (DIN EN 60715 TH35) in
the control cabinet. The safety evaluation unit is fixed.
- Connect the safety control unit.
The pluggable terminal blocks can be coded by means of pins, the sockets
in the device are inversely coded by means of coding tabs.
- If the safety input remains free:
Ensure that the NO contacts of this safety input are bridged.
10 Electrical connection
- Installation and electrical connection are only permitted in a de-energized state.
- Ensure that the specifications described in the technical specifications are met.
- Measures must be taken to improve the equipment's immunity to conducted
and radiated radio frequency interference (DIN EN 60204-1:2019-06).
When connecting a sensor, the sensor supply voltage (+) and (-) must be used
from the terminals specified in the technical specifications.
Terminal assignment (standard)
Components
Safety input 1
Safety input 2
Safety input 3
Safety input 4
Safety output 1
Safety output 2
Safety output 3
Safety output 4
EDM/Start 1–2
Operating voltage
Control output 1
Control output 2
Control output 3
Control output 4
(see "Technical
Accessories
Spring-loaded terminals (order no. 2x 878598VPE4; 4 con-
nectors per packaging unit) and a corresponding coding rider
set (order no. 350SAE001) can be ordered as standard.
Screw terminal (order no. 2x 878719VPE4; 4 terminals per
packaging unit) and double terminals (order no. 2x
878717VPE4; 4 terminals per packaging unit) are optionally
available from elobau.
Terminals Explanation
5–8
Depending on configuration, the inputs at
terminals 5, 13, 21, 29 (+) or (-) are read-only.
13–16
Connection options:
21–24
- Sensors with 2 NO system
29–32
- Sensors with NO/NC contact system
- Emergency stop button
- Two-hand control
- Light grid (OSSD)
- Electronic sensors (OSSD)
switching dependent upon:
1, 25
- Safety input 1–4
- Logic
2, 26
- Switch-on/switch-off delay times (optional)
3, 27
- EDM/start inputs (optional)
4, 28
11, 12
EDM and/or start button (automatic, manual,
or monitored)
9, 10
17
switching dependent upon:
18
Error:
19
- Control output is set in case of input error
20
(input state disabled) and two-hand
error (ZHS state disabled)
- Safety input 1–4
- Logic
- Switch-on/switch-off delay times (optional)
Datum/Date/Date/Data/Fecha: 09.08.2023
Fig. 2
specifications"
from
6/22