2.2.2 Connection of the control circuit
In order to prevent a malfunction caused by interference voltage supply on the control inputs, the following
directions should be observed:
•
Use shielded / drilled cables
•
Lay shield on one side of the inverter onto earth potential
•
Lay control and power cable separately (about 10...20 cm apart); Lay crossings in a right angle (in
EMC
case it cannot be prevented)
2.2.3 Digital Inputs
13...30 V DC ±0 %
stabilized
Ri = 2,1 kΩ
2.2.4 Analog Inputs
Connect unused analog inputs to common, to prevent set value fluctuations !
Analog set value setting in speed regulated operation (CP.10 = 4):
Ri = 55 k�
X2A
0...±10 VDC
Analog set value setting in torque regulated operation (CP.10 = 5) and reference source CP.28 = 1:
*)
Connect potential equalizing line only if a potential difference of >30 V exists between the controls.
The internal resistance is reduced to 30 kΩ.
Using of the internal voltage supply
X2A
10 11 12 13 14 15
Using of an external voltage supply
X2A
10 11 12 13 14 15
external
1 2 3 4 5 6 7 8 9
*)
+
Ri = 55 k�
X2A
1 2 3 4 5 6 7 8 9
0...±10 VDC
16 17
20 21 22 23
16 17
20...30 V DC
internal
X2A
PE
1 2 3 4 5 6 7 8 9
PE
*)
+
PE
23
PE
+
PE
R = 3...10 k�
GB