Parameter description
CP.35
Limit switch / stopping mode
This parameter determines the reaction of the drive, to terminal X2A.14 (F) and/or X2A.15 (R). These terminals
are programmed as limit switches. The reaction of the drive is shown in the table below.
Value
Setting
0
1
2
3
GB
4
5
6
CP.36
Reaction to external fault
With the external error monitoring external units can take direct influence on the drive. This parameter determines
the response of the drive to a signal at terminal X2A.12 (I3) according to following table.
Value
Setting
0
1
2
3
4
5
6
GB - 22
Display
Reaction
E.PRx
Immediate disabling of modulation
Quick stopping / disabling of modulation after reaching
A.PRx
speed 0
A.PRx
Quick stopping / holding torque at speed 0
A.PRx
Immediate disabling of modulation
Quick stopping / disabling of modulation after reaching
A.PRx
speed 0
A.PRx
Quick stopping / holding torque at speed 0
x
—
No effect to the drive, fault is ignored !
Display
Reaction
x
E.PRx
Immediate disabling of modulation
Quick stopping / disabling of modulation after reaching
A.PRx
speed 0
A.PRx
Quick stopping / holding torque at speed 0
A.PRx
Immediate disabling of modulation
Quick stopping / disabling of modulation after reaching
A.PRx
speed 0
A.PRx
Quick stopping / holding torque at speed 0
—
No effect to the drive, fault is ignored !
Restart
Remove fault,
reset
Autoreset, if no fault
is present
—
Restart
Remove fault,
reset
Autoreset, if no fault
is present
—