Error Assistance
Display
COMBIVIS
E. OC
Error ! overcurrent
E. OH
Error ! overheat pow.mod.
E.OH2
Error ! motor protection
E.OHI
Error ! overheat internal
E. OL
Error ! overload (Ixt)
E.OL2
Error ! overload 2
E. OP
Error ! Overvoltage
E.OS
Error ! over speed
E.PFC
Error ! Power factor control
E.PrF
Error ! prot. rot. for.
E.Prr
Error ! prot. rot. rev.
E. Pu
Error ! power unit
E.Puci
Error ! Unknown power unit
Meaning
Occurs, if the specified peak current is exceeded. Causes:
acceleration ramps too short
the load is too big at turned off acceleration stop and turned off constant
current limit
short-circuit at the output
4
short-circuit at the output
deceleration ramp too short
motor cable too long
EMC
DC brake at high ratings active (see 6.9.3)
Error: Overtemperature of power module. Error can only be reset at
E.nOH. Causes:
insufficient air flow at the heat sink (soiled)
8
ambient temperature too high
ventilator clogged
30
Electronic motor protective relay has tripped.
Error: Overheating in the interior: error can only be reset at E.nOHI, if
6
the interior temperature has dropped by at least 3 °C.
Error: Overload error can only be reset at E.nOL, if OL-counter reaches
0% again. Occurs, if an excessive load is applied longer than for the
permissible time (see technical data). Causes:
poor control adjustment (overshooting)
16
mechanical fault or overload in the application
inverter not correctly dimensioned
motor wrongly wired motor wrongly wired
encoder damaged
Occurs if the standstill constant current is exceeded (see technical data
19
and overload characteristics). The error can only be reset if the cooling
time has elapsed and E.nOL2 is displayed.
Voltage in the DC-link circuit too high. Occurs when the DC bus voltage
rises above the permissible value. Causes:
poor controller adjustment (overshooting)
input voltage too high
1
interference voltages at the input
deceleration ramp too short
braking resistor defective or too small
58
Real speed is bigger than the max. output speed.
33
Error in the power factor control
The drive has driven onto the right limit switch. Programmed response
46
„Error, restart after reset" (see chapter 6.7 „Response to errors or
warning messages").
The drive has driven onto the left limit switch. Programmed response
47
„Error, restart after reset" (see chapter 6.7 „Response to errors or
warning messages").
12
Error: General power circuit fault
Error: During the initialization the power circuit could not be recognized
49
or was identified as invalid.
GB
further on next side
GB - 27