Installing and Wiring the Drive
Table 2.5 – Programmable Digital Input Functions
Function
The motor voltage will be switched off immediately and the motor will
coast. This function can be programmed to operate in two different
modes via parameter b88 [FRS Select].
Input 11 {FRS} (NO)
Note: The drive will start when 11 {FRS} input is removed without
reissuing a start command even if in 3-wire (momentary) control.
When this input is active, an E12 fault indication will be issued (e.g. an
input received from thermal contacts). The fault indication will be
cleared with a reset 18 {RS}.
Important: After a reset 18{RS} command, the drive will start again if a
Input 12 {EXT} (NO)
Input 18 {RS} (NO)
Fault relay (AL0-Al2) (NO)
This function is designed to guard against unintended starting when
input power is removed and then restored. In this case, if a start/run
command is issued immediately upon/after power is restored an E13
fault will be issued. A new start command or a reset 18 {RS} command
will clear the fault indication.
Power Supply
00{FW} or
01 {RV} (N.O.)
13 {USP}(N.C.)
Fault relay (N.O.)
Motor Speed
Protects stored parameter values from being overwritten. See
parameter b31 [
protection.
Description
synchronization of
motor speed
Run (NO)
Motor Speed
Waiting time
start command is active (00{FW}, 01{RV},or 20 {STA}).
Run (NO)
Motor Speed
PROGRAM LOCK SELECT
0 Hz start
Motor will
Coast
Min. 3 Sec
] for the 4 different levels of