Overoad capacity
Starting torque
Inherent Braking Torque
DC brake
Analog inputs
Digital inputs
Analog outputs
Digital outputs
Relay output
Protection functions
Other functions
Ambient temperature
Relative humidity
Vibration/Shock
Max. Installation altitude 1000 m (3300 ft) above sea level
Options
Standards
A-2
Software: 150% for 60 sec (once in 10 min); Hardware: 220%
minimum 100% or more (when torque boost has been set)
S12-201P4 ...204P0: 100%
S12-205P0 ...207P1: 70%
S12-20010 ...20015:
20%
(approximate; actual values depend on motor characteristics)
Starting frequency, braking torque, running times are variable
0 to 10 V, input impedance 10 k
4 to 20 mA, input impedance 250
PTC input
5 programmable level-triggered inputs, 24 V PNP logic, NO or NC contacts
1 programmable analog output, 0 to 10 V, 1 mA
Accuracy: +5% for frequency, + 20% or current
2 open collector outputs; 27 VDC, 50 mA
1 fault indication relay (change-over contact)
Resistive rating: 2.5 A at 250 VAC; 3 A at 30 VDC
Inductive rating: 0.2 A at 250 VAC; 0.7 A at 30 VDC
Overcurrent, overvoltage, undervoltage, electronic motor protection,
overtemperature, ground fault
15 preset speeds, PID control, unintentional start protection,
RS422 serial interface, skip frequencies
°
-10 to +40
C (up to +50
2 kHz, and derating output by 20%)
20 to 90% relative hmidity, no condensation
Vibration: 0.6 G operational / Shock: 10.0 G operational
Line filter modules
EN 61800-3 EMC guidelines in connection with optional line filter modules in line
with installation guidelines
EN 50178 Low Voltage guideline
UL508C
CSA 22.2
®
®
O
O
CE applies to 230 VAC and 460 VAC units.
Ω
Ω
°
C by removing top cover, reducing carrier frequency to
N223
(pending)
SP120 AC Drive Installation and Operation