Parameter
Number
DC Brake
A51
DC Brake Enable
Used to enable/disable DC injection braking
Settings: 00=Disabled
01=Enabled
A52
DC Brake Start Frequency
Sets the frequency at which the DC brake will become
active.
A53
DC Brake Wait Time
Sets the time the drive will wait after A52 [
START FREQUENCY
].
VOLTAGE
A54
DC Hold Voltage
Sets the level of DC braking voltage in percent of A82
[
BASE VOLTAGE
A55
DC Hold Time
The time that A54 [
motor after A53 [
Operating Frequency Range
A61
Upper Frequency Limit
This is an upper frequency limit similar to A04 [
FREQUENCY
[
BASE FREQUENCY
parameter.
Output Frequency
A61
A62
A62
Minimum Frequency
Lowest frequency the drive will output continuously.
Refer to diagram in A61 [
A63
Skip Frequency 1
Sets a frequency at which the drive will not output
continuously.
A64
Skip Frequency Band 1
Sets the bandwidth around A63 [
The bandwidth is 2x A64 [
½ the band below and ½ the band above A63 [
FREQUENCY
A65
Skip Frequency 2
Sets a frequency at which the drive will not output
continuously.
Parameters and Programming
Parameter Name/ Description
] before applying A54 [
].
DC HOLD VOLTAGE
DC BRAKE WAITING TIME
] except that it can be set lower than A03
]. A value of 0.0 will disable this
Frequency Command
UPPER FREQUENCY LIMIT
SKIP FREQUENCY
SKIP FREQUENCY BAND
1].
Min./Max
00 to 01
0.5 to 10.0
0.0 to 5.0
DC BRAKE
DC HOLD
0 to 100
0.0 to 60.0
] is applied to the
] has expired.
0.5 to 360.0 0.1Hz
MAXIMUM
0.0 to 360.0 0.1Hz
].
0.0 to 360.0 0.1Hz
0.0 to 10.0
1].
1] with
SKIP
0.0 to 360.0 0.1Hz
Range
Units
Numeric
Value
0.1 Hz
0.1 sec
1% of drive
rating
0.1 sec
0.1Hz
English
Factory
Default
00
10.0
0.0
0
0.0
0.0
0.0
0.0
0.5
0.0