Parameter
Number
Operating Frequency Range (continued)
A66
Skip Frequency Band 2
Sets the bandwidth around A65 [
The bandwidth is 2x A66 [
½ the band below and ½ the band above A65 [
FREQUENCY
A67
Skip Frequency 3
Sets a frequency at which the drive will not output
continuously.
A68
Skip Frequency Band 3
Sets the bandwidth around A67 [
The bandwidth is 2x A68 [
½ the band below and ½ the band above A67 [
FREQUENCY
PID Controller
A71
PID Enable
Used to disable / enable the use of PID control.
Settings: 00=disable
01=enable
(See Appendix B for the PID block diagram)
A72
PID Proportional Gain*
Sets the proportional gain for PID control.
This parameter can be changed while motor is running.
A73
PID Integral Gain*
Sets the integral gain for PID control.
This parameter can be changed while motor is running.
A74
PID Differential Gain*
Sets the differential gain for PID control.
This parameter can be changed while motor is running.
A75
Process Reference Scale Factor
Used to scale the target value equivalent to the PID
feedback value.
A76
Analog Feedback Select
Selects the source from which the PID feedback
originates
Settings: 00=Input OI
01=Input O
Automatic Voltage Regulation (AVR)
A81
AVR Function Select
Used to select the Automatic Voltage Regulation
function.
Settings: 00=Active
01=Inactive
02=Inactive during deceleration
A82
Base Voltage
Set voltage to rated nameplate voltage of motor.
3-14
Parameter Name/ Description
SKIP FREQUENCY
SKIP FREQUENCY BAND
2].
SKIP FREQUENCY
SKIP FREQUENCY BAND
3].
Min./Max
Range
0.0 to 10.0
2].
2] with
SKIP
0.5 to 360.0 0.1Hz
0.0 to 360.0 0.1Hz
3].
3] with
SKIP
00/01
0.2 to 5.0
0.0 to 150.0 0.1 sec
0.0 to 100.0 N/A
0.01 to 99.99 N/A
00 to 01
00 to 02
200 to 460
SP120 AC Drive Installation and Operation
Factory
Units
Default
0.1Hz
0.5
0.0
0.0
Numeric
00
Value
N/A
1.0
1.0
0.0
1.00
Numeric
00
Value
Numeric
02
Value
10 Volts
230 or
460