Parameter
Number
Digital Inputs 1 – 5 (continued)
C11
Digital Inputs 1-5 Logic
Sets the digital inputs to be NO or NC contacts
C12
Settings: 00=NO contact (active high)
C13
01=NC contact (active open)
C14
C15
Outputs 11, 12, FM, AL0-AL1
C21
Digital Outputs 11-12
Sets the operation of the digital outputs
Settings: 00={RUN} (Motor running above 0.5 Hz)
01={FA1} (At frequency and above 0.5 Hz)
02={FA2} (Above frequency)
03={OL} (Overload alarm)
C22
04={OD} (PID deviation)
05={AL} (Fault)
Refer to control terminal table in chapter 2 for setting
descriptions.
C23
Output FM Select
Sets the operation of the output FM.
Settings: 00={A-F} (Analog Output Frequency)
01={A} (Motor Current)
02={D-F} (Digital Output Frequency)
Refer to control inputs table in chapter 2 for setting
descriptions.
C31
Digital Output 11-12 Logic
Sets the digital outputs to be NO or NC contacts.
C32
Settings: 00=NO contact (Active high)
01=NC contact (Active open)
C33
Fault Relay AL1 Logic
Sets the fault relay to be either NO or NC contacts.
Settings: 00 = NO contact (active high)
01 = NC contact (active open)
Refer to control inputs table in chapter 2 for setting
descriptions.
C41
Overload Alarm Threshold
Sets the allowable overload level before digital outputs
11-12 change state when set to 03 {0L}.
C42
Above Frequency Accel Threshold
Sets the frequency at which digital outputs 11-12
change state when set to 02 {FA2} if the drive is
accelerating.
C43
Above Frequency Decel Threshold
Sets the frequency at which digital outputs 11-12
change state when set to 02 {FA2} if the drive is
decelerating.
C44
PID Deviation Threshold
Sets the allowable PID Loop error before digital outputs
11-12 change state when set to 04 {OD}.
3-20
Parameter Name/Description
Min./Max
Range
Units
00 to 01
Numeric
Value
00 to 05
Numeric
Value
00 to 02
Numeric
Value
00 to 01
Numeric
Value
00 to 01
Numeric
Value
0 to 200% of
0.01 A
drive rating
0.0 to 360.0 0.1 Hz
0.0 to 360.0 0.1 Hz
0.0 to 100% +/- 0.1%
SP120 AC Drive Installation and Operation
Factory
Default
00
00
01
00
01
01
00
00
00
00
01
100% of
drive rating
0.0
0.0
+/-3.0